1. Where are gauges located on a wet pipe sprinkler system? - ANSWER ✓ On
the water supply and the service side.
2. What is the retard chamber for? - ANSWER ✓ It pre-fills with water during
surges prior to allowing water to the electronic alarm thus preventing false
alarms. its piped out from the supply side of a wet pipe sprinkler under the
clapper or before the clapper.
3. What is the purpose of a one way clapper? - ANSWER ✓ to prevent water
from re entering the water supply.
4. what is an inspectors test valve? and where is it usually located? - ANSWER
✓ An inspectors test valve is a valve used to drain the system tricking it into
thinking a sprinkler head set off. This is used to test if the system is working.
This system is located at the farthest branch of a sprinkler system.
5. Glass bulb sprinkler - ANSWER ✓ operated by heat breaking a glass bulb
filled with a non freezing liquid with diameters that vary form 3 mm for
quick response to 5 mm for standard response
6. hose valve - ANSWER ✓ valve to additional hose connection
,7. hydraulic placard - ANSWER ✓ sign attached to a hydraulically calculated
sprinkler system indicating the design density, required gallons per minute
and pressure for the system to operate properly
8. hydraulically calculated systems - ANSWER ✓ method of sizing auto
sprinkler piping using a prescribed amount of water to be distributed over a
specific area.
9. impairment coordinator - ANSWER ✓ in charge of safety during out of
service systems
10.intermediate level sprinkler - ANSWER ✓ sprinkler equipped with integral
shields to protect the operating elemtn form discharge from sprinklers
installed at higher elevations
11.large orifice sprinkler - ANSWER ✓ sprinkler head with orifice size equal or
greater than 3/4 and less than 1 inch
12.listed device - ANSWER ✓ A fire protection component that has been tested
to perform under parameters specified for its use by a nationally recognized
testing agency. Underwriter's Laboratory (UL) and Factory Mutual (FM) are
the two most common.
13.Master Pressure Reducing Valve - ANSWER ✓ A pressure reducing valve
installed to regulate pressures in an entire fire protection system and/or
standpipe system zone.
14.Main Drain - ANSWER ✓ The primary drain connection located on the
system riser and also utilized as a flow test connection.
15.Microbiologically Influenced Corrosion (MIC) - ANSWER ✓ Corrosion
caused by the presence of microbes in the water supply that over time attack
the interior of metallic piping and cause leaks, pitting, and blockages.
16.Conventional Sprinkler - ANSWER ✓ A sprinkler that directs 40% to 60%
of the water initially in a downward direction and is designed to be installed
with the deflector in either the upright or pendent position.
,17.Pendent Sprinkler - ANSWER ✓ A sprinkler designed to be installed in such
a way that the water stream is directed downward against the deflector.
18.Pintle Screws - ANSWER ✓ A visual indicating device required for
sprinklers manufactured prior to 1999 identifying small orifice sprinklers
and large orifice sprinklers where orifice size is different than the nominal
thread size of the sprinkler head.
19.Pipe Schedule Systems - ANSWER ✓ A method of sizing piping based
upon the number of sprinkler heads and the occupancy of the protected area.
20.Preaction Sprinkler System - ANSWER ✓ A sprinkler system employing
automatic sprinklers that are attached to a piping system that contains air
that may or may not be under pressure, with a supplemental detection system
installed in the same areas as the sprinklers.
21.Pressure Control Valve - ANSWER ✓ A pilot operated pressure reducing
valve that may be used with a fire or booster pump designed for the purpose
of preventing the incoming water supply pressure from dropping below a set
pressure.
22.Pressure-Reducing Valve - ANSWER ✓ A valve designed for the purpose of
reducing the downstream water pressure under both flowing (residual) and
nonflowing (static) conditions.
23.Pressure Relief Valve - ANSWER ✓ A valve designed for the purpose of
releasing excess air or water pressure from the Fire Protection Piping
System.
24.Pressure Tank - ANSWER ✓ A tank using air pressure to supplying water
for water-based fire protection systems. Tank contents to be maintained at
one third air to two thirds water.
25.Quick Response Sprinkler Head - ANSWER ✓ A sprinkler having a fusible
link with a response time index (RTI) of 50 or less.
, 26.Recessed Sprinkler - ANSWER ✓ A sprinkler in which all or part of the
body, other than the shank thread, is mounted above the ceiling.
27.Residential Sprinkler - ANSWER ✓ A type of fast response sprinkler that
has been specifically tested to enhance survivability in the room of fire
origin and listed for use in dwelling units.
28.Response Time Index (RTI) - ANSWER ✓ A measurement of the thermal
sensitivity of a sprinkler head expressed in (meters-seconds) 1/2.
29.Supervisory signal - ANSWER ✓ A signal indicating the need for action or
the use of such device in connection with the supervision of fire alarm
systems or the maintenance features of related systems.
30.Small orifice sprinklers - ANSWER ✓ A sprinkler head with and orifice size
smaller than 1⁄2"
31.Solder Link Sprinkler - ANSWER ✓ A sprinkler operated by the melting of
a metal link, they vary in size and configuration for quick response and
standard response sprinklers. The smaller the size of the link, the faster the
sprinkler operates.
32.Spray Sprinkler - ANSWER ✓ A type of sprinkler listed for its capability to
provide fire control for a wide range of fire hazards. The most commonly
used sprinkler since 1953.
33.Standard Response Sprinkler Head - ANSWER ✓ A sprinkler having a
fusible link with a response time index (RTI) of 80 or more.
34.Supervisory signal-initiating device - ANSWER ✓ An initiating device, such
as a valve supervisory switch,that triggers a supervisory signal.
35.Testing - ANSWER ✓ A procedure used to determine the status of a system
as intended by conducting periodic physical checks on water based fire
protection systems such as waterflow tests, fire pump tests, alarm tests, and
trip tests of dry pipe, deluge, or preaction valves. These tests follow up on
the original acceptance test at intervals specified in the appropriate chapter
of NFPA #25, 2002 edition.