1. The air receiver - ANSWER ✅Water builds up in the moisture
separator assembly and the air receiver must be drained daily;
however, there is one exception. Do not drain moisture from the air
compressor when the
ambient temperature drops below 40 degrees Fahrenheit. This is
done by opening the drain
valve and draining off the excess water. All safety valves should be
manually operated every
week. This is to ensure that they will function correctly in case of
an emergency. It is
recommended that the air receiver tank be pressure tested at a
minimum of every 5 years by a
qualified technician.
2. The Hose Connections - ANSWER ✅All hose connections on
the air compressor should be checked frequently by the Certificate
of
Fitness holder to make sure that they are tight. Never twist, bend or
curl an air hose to stop the
air hose. That's the job of the air valve. You should not patch a
leaking hose with duct tape. You
can replace the hose, or you can repair the leak by cutting out the
bad section and joining the
hose back together with a connector and clamps. The safety valves
and gauges should be
1