1. The __________ is responsible to owner
maintain sprinkler sys. and to
determine qualifications.
2. Records of all inspections and Three
maintenance shall be kept on
premises for a minimum of
__________ years.
3. The building owner shall assign Impairment Coordinator
a(n) ____________ to comply with
requirements.
4. Regular maintenance and mi- One
nor repairs not affecting more
than ________ floor(s) are consid-
ered planned removal from ser-
vice.
5. Shutdowns affecting more than One
_________ floor(s) are considered
unplanned out of service condi-
tions.
6. Notification to the FDNY is Eight
not required, provided system
is returned to service within
_________ hours.
7. For an unplanned removal from Owner of the building
service, the COF holder shall im-
mediately report condition to
, FDNY S-12 CITYWIDE SPRINKLER SYSTEMS
the ___________ and the Fire Dep-
tartment.
8. If a minor defect is observed, 30
it shall be corrected within
_________ days or it will be con-
sidered an impairment.
9. What does "O.O.S." stand for? OUT OF SERVICE
10. O.O.S systems shall be identi- Tags
fied by placing ________ at Fire
Department connections, sys-
tem control valves, and the Fire
Command Center.
11. A _______ shall be required to Master Fire Suppression Piping Contractor
post tags at main control valve
and any sectional valves.
12. __________ shall be posted on the Drain test results.
tag indicating both static and
flow pressures before and after.
13. Green tags indicate that No impairment was found.
__________.
14. Green tags will be placed on the Main Control Valve
____________.
15. Systems partially or fully out of Red
service shall have a ____________
tag placed on the main control
valve.
, FDNY S-12 CITYWIDE SPRINKLER SYSTEMS
16. A _________ disc of 8-9 inches White
shall be placed on connections
to indicate the system is fully
out of service.
17. A ________ disc of 8-9 inches shall Blue
be placed on connections to in-
dicate the system is partially out
of service.
18. The Impairment Coordinator Insurance
will notify the ___________ carrier,
central station and occupants.
19. Prior to returning a sprin- Impairment Coordinator
kler system to service, the
___________ shall ensure that
necessary tests and inspections
are conducted.
20. Glycerin not greater than 50 and 40
_________ percent or glycol not
greather than ________ percent
shall be used to protect from
freezing.
21. The C.O.F. number and signa- Main Control Valve
ture of C.O.F. holder shall be
posted near the ____________.
22. __________ shall be readily avail- Records
able to any representative of the