NYC RMO EXAM, CHAPTER 25 (Thermostatic
Expansion Valves) questions with verified answers
25.01.) TEVs are usually rated by? Ans✓✓-Tons of refrigeration
25.02.) Which of the following does a TEV control? Ans✓✓-Flow of refrigerant to
the evaporator
25.03.) When installing a TEV sensing bulb, where should it be placed to assure
correct operation? Ans✓✓-At the end of the evaporator
25.04.) Which of the following operational conditions does the TEV attempt to
maintain at a constant value? Ans✓✓-Superheat temperature
25.05.) Upon inspecting a TEV installation, you find that the sensing bulb is
clamped to the evaporator directly after the valve. Which of the following would
you expect to take place? Ans✓✓-The valve will not feed enough refrigerant and
the coil will starve
25.06.) A finned coil evaporator is equipped with a TEV. The bulb of this valve is
properly clamped to the end of the coil. In what condition should the suction
vapor leaving the coil be? Ans✓✓-5 to 10 degrees F (superheated)
25.07.) In a Freon air conditioning system, the bulb of a TEV has been clamped at
the midpoint of the evaporator being served. How will this affect the coil
operation? Ans✓✓-The refrigerant leaving the coil will be excessively
superheated
Expansion Valves) questions with verified answers
25.01.) TEVs are usually rated by? Ans✓✓-Tons of refrigeration
25.02.) Which of the following does a TEV control? Ans✓✓-Flow of refrigerant to
the evaporator
25.03.) When installing a TEV sensing bulb, where should it be placed to assure
correct operation? Ans✓✓-At the end of the evaporator
25.04.) Which of the following operational conditions does the TEV attempt to
maintain at a constant value? Ans✓✓-Superheat temperature
25.05.) Upon inspecting a TEV installation, you find that the sensing bulb is
clamped to the evaporator directly after the valve. Which of the following would
you expect to take place? Ans✓✓-The valve will not feed enough refrigerant and
the coil will starve
25.06.) A finned coil evaporator is equipped with a TEV. The bulb of this valve is
properly clamped to the end of the coil. In what condition should the suction
vapor leaving the coil be? Ans✓✓-5 to 10 degrees F (superheated)
25.07.) In a Freon air conditioning system, the bulb of a TEV has been clamped at
the midpoint of the evaporator being served. How will this affect the coil
operation? Ans✓✓-The refrigerant leaving the coil will be excessively
superheated