Class A/B Operator for Underground
Storage Tank. Study Exam Questions With
Correct Answers
The Class A and Class B certification must be renewed every: - answer✔5 years
UST financial responsibility requirements apply to what? - answer✔600 gallon used oil tank
Secondary Containment is required for what? - answer✔New UST Systems, Piping in contact
with the ground, and Replacement UST
A Class A operator shall maintain the records of UST site inspections for a *minimum* of: -
answer✔3 years
New owners of an existing UST system shall register the UST system with DEQ/LARA within
what period from date of ownership? - answer✔30 days
UST systems with cathodic protection should be inspected for proper operation by a qualified
cathodic protection tester on the following schedule: - answer✔Every three years
UST systems with impressed current cathodic protection systems must be inspected at a
minimum: - answer✔Every 60 days
Within what period after a repair should a cathodically protected UST system be tested to
ensure it is working properly? - answer✔6 months
Pressurized underground piping that routinely contains regulated substances shall be
monitored for releases in a manner that meets what requirements? - answer✔Be equipped
with a line leak detector, and have an annual line tightness test
A suspected release must be confirmed to the DEQ/LARA within: - answer✔7 days
What actions are required in MUSTR when there is a spill or overfil of petroleum or hazardouz
substances that result in a release into groundwater, surface water, or substance soils? -
1|Page
, ©BRAINBARTER EXAM SOLUTIONS 2024/2025
ALL RIGHTS RESERVED.
answer✔Notify DEQ/LARA of a confirmed release, Immediately clean up the spill or overfill, and
Contain the spill
To permanently close a tank, an owner and operator shall: - answer✔Remove the tank from the
ground, Fill with an inert solid if removal jeopardizes the building structure integrity, and Empty
and clean the tank by removing all liquids and accumulated sludge and purge it of all vapors
If you have 100 or fewer tanks, financial responsibility is required in the aggregate the amount
of: - answer✔$1 Million
Petroleum marketers are required to have finanical responsibility to cover X dollars per
occurence. X is.... - answer✔$1 Million
Can an owner use pollution liability insurance as a means of financial responsibility? -
answer✔Yes
An automatic tank gauge must be able to detect a leak of X gallons per hour. X is: - answer✔0.2
gallons per hour
Statistical Inventory reconciliation (SIR) analyzes the following as a means of leak detection: -
answer✔Inventory, Delivery and Dispensing
Manual tank gauging can be used as the 'sole' means of a leak detection for tanks that are X
gallons or less in capacity. X is: - answer✔550 gallons
Check if the following statement is true or false: "A third party evaluation of a statistical
inventory reconciliation is good for any type of tank and product." - answer✔False
Automatic line leak detectors must be able to detect a leak of at least X gallons per hour at a
line pressure of 10 psi witin one hour. X is: - answer✔3 gallons per hour
Line testing of piping shall be capable of detecting X gallons per hour leak rate at 1 and a half
times the operating pressure. X is: - answer✔0.1 gallons per hour
What actions are not appropriate when when the owner/operator becomes aware of a spill or
overfill? - answer✔Drain the spill to the storm sewer or nearby ditch
Upon confirmation of a release to the soil/groundwater/surface water the operator shall: -
answer✔Report the release to the DEQ within 24 hours, by fax or phone
A Class B operator shall not be responsible for more than the following facilities: - answer✔45
facilities
What is the minimum frequency of site inspections to assure operational compliance? -
answer✔Quarterly