Type 3 - answer-Technicians maintaining, servicing, repairing or disposing of low-
pressure appliances must be certified as a universal technician or a _______ ___.
Enter - answer-Because a low-pressure system operates below atmospheric
pressure (in a vacuum), leaks in the gaskets or fittings will cause air and moisture
to ______ the system.
Heater - answer-The most efficient method of leak checking a charged, low-pressure
refrigeration unit is to pressurize the system by the use of controlled hot water or
______ blankets.
Nitrogen - answer-When unable to heat a low-pressure system for leak-checking,
use ______ to increase pressure.
10 - answer-When pressurizing a low-pressure system with nitrogen, do not exceed
_____ psig.
Rupture - answer-Exceeding 10 psig when pressurizing a low-pressure system, can
cause the _____ disc to fail.
Removed - answer-When leak testing a water box, be certain the water has been
______ before placing the leak detector probe through the drain valve.
Hydrostatic - answer-When leak-testing a tube, use a _______ tube test kit.
Seal - answer-Systems with open drive compressors are prone to leaks at the shaft
_____.
Hot - answer-For the purpose of opening the system for a non-major repair,
controlled ______ water can be used to pressurize a system.
High pressure - answer-A recovery unit's _____ _____ cut-out is set for 10 psig when
evacuating the refrigerant from a low-pressure chiller.
15 - answer-A low-pressure chiller and a rupture disc on a low-pressure recovery
vessel relieves at _____ psig.
Liquid vapor - answer-Refrigerant recovery from a system using R-11 or R-123
starts with ______ removal and is followed by _____ recovery.
Vapor - answer-A substantial amount of _____ will remain in the appliance after all
liquid is removed.
100 - answer-An average 350 ton R-11 chiller at 0 psig still contains _____ lbs. Of
vapor after all the liquid has been removed.