SYSTEMS TEST |GUARANTEED
PASS
The __________ is responsible to maintain sprinkler sys. And to
determine qualifications. - accurate answers✔✔ owner
Records of all inspections and mx shall be maintained on premises for a
min. Of __________ years. - accurate answers✔✔ 3
The building owner shall assign a(n) ____________ to comply with
requirements. - accurate answers✔✔ impairment coordinator
Regular mx and minor repairs not affecting more than ________ floor(s)
are considered planned removal from service. - accurate answers✔✔ 1
Shutdowns affecting more than _________ floor(s) are considered
unplanned out of service conditions. - accurate answers✔✔ 1
Notification to fdny is not required, provided system is returned to
service within ______ hours. - accurate answers✔✔ 8
For unplanned removal from service, the cof holder shall immediately
report condition to the ___________ and the fire dept. - accurate
answers✔✔ owner of the building
,If a minor defect is observed, it shall be corrected within _________
days or it will be considered an impairment. - accurate answers✔✔ 30
What does "oos" stand for? - accurate answers✔✔ out of service
Oos systems shall be identified by placing ________ at fire dept.
Connections, sys. Control valves, and fire command center - accurate
answers✔✔ tags
A _______ shall be required to post tags at main control valve and any
sectional valves. - accurate answers✔✔ master fire suppression piping
contractor
__________ shall be posted on the tag indicating both static and flow
pressures before and after. - accurate answers✔✔ drain test results
Green tags indicate that __________. - accurate answers✔✔ no
impairment was found
Green tags will be placed on the ____________. - accurate answers✔✔
main control valve
Systems partially or fully out of service shall have a ____________ tag
placed on the main control valve. - accurate answers✔✔ red
, A _________ disc of 8-9 inches shall be placed on connections to
indicate the system is fully out of service. - accurate answers✔✔ white
A ________ disc of 8-9 inches shall be placed on connections to indicate
the system is partially out of service. - accurate answers✔✔ blue
The impairment coordinator will notify the ___________ carrier, central
station and occupants. - accurate answers✔✔ insurance
Prior to returning a sys. To service, the ___________ shall ensure that
necessary tests and inspections are conducted. - accurate answers✔✔
impairment coordinator
Glycerin not greater than _________ percent or glycol not greather than
________ percent shall be used to protect from freezing. - accurate
answers✔✔ 50, 40
The cof number and signature of cof holder shall be posted near the
____________. - accurate answers✔✔ main control valve
__________ shall be readily available to any representative of the fire
dept. These are to be maintained on site for 3 years. - accurate
answers✔✔ records
Failure to make inspections may result in __________ of the cof and
court proceedings. - accurate answers✔✔ revocation