Texas Fire Alarm Rules & Statutes Exam Questions & Answers Graded A
Texas Fire Alarm Rules & Statutes Exam Questions & Answers Graded A Both audible and visual alarm indication shall be supervised - ANSWERTrue Speakers are permitted for voice communication only - ANSWERFalse Private Mode audible signal appliance minimum sound level of - ANSWER45 dBA at 10' -- 10 dBA above average, 5 dBA above maximum sound level; whatever is greater measured at 5' above floor. A signal indicating an emergency requiring immediate action is an - ANSWERalarm signal Where Public Mode audible appliances are installed they shall be ____________ above average ambient sound level - ANSWER15 dBA An alarm silencing switch, a means for silencing the trouble notification appliance shall be permitted only if _________ - ANSWERIt is key-operated or located within a local cabinet It will give a trouble signal if left in the "silence" position when no alarm exists It will transfer indication of an alarm to a visual indicator What
Información del documento
- Subido en
- 25 de noviembre de 2023
- Número de páginas
- 47
- Escrito en
- 2023/2024
- Tipo
- Examen
- Contiene
- Preguntas y respuestas