Texas Fire Alarm Rules And Statutes FAL TFM12 BFAT3 Exam Questions With Correct Answers! Where supervised automatic sprinkler systems are required by Code, which standard or code regulates supervisory attachment installation? - ANSWERNFPA 72, National Fire Alarm Code A colorless, odorless, electrically non-conductive inert gas that extinguishes fire and forms dry ice snow when released directly into the atmosphere - ANSWERCarbon dioxide gas An automatic smoke detector that requires continuous presence of smoke above the alarm threshold for more than 1 minute before initiating an alarm is said to equipped with which feature below? - ANSWERAlarm Verification Fire Alarm conductors in Class 1, Division 1 locations shall be - ANSWERMulti or single conductor Copper in IMC or GRC The following wiring methods are not permitted for Fire Alarm conductors installed in Class 1 Division 2 locations - ANSWERnone of the above, all are acceptable methods Fire Alarm equipment shall be durably marked where plainly visible to indicate each circuit - ANSWERThat is is Power-limited fire alarm circuit Smoke detectors listed for use in air distribution systems moving more that 2000ft3/min shall be located - ANSWERon the supply air side downstream of the air filters