EXAM ELABORATIONS IRC
BUILDING CERTIFICATION TEST
WITH ACCURATE ANSWERS
◉ In Seismic Design Categories Do, D1 and D2, foundations with
stem walls shall be provided with a minimum of one No. ___ bar
within 12 inches of the top of the wall and one No. ___ bar located 3
to 4 inches from the bottom of the footing. Answer: #4
#4
R403.1.3.1 Foundations with stemwalls
◉ The grade away from foundation walls shall fall a minimum of ___
inches within the first ____ feet. Answer: 6 in.
10 ft.
(Read exception)
R401.3 Drainage
◉ In flood hazard areas, enclosed areas below the design flood
elevation shall be used sole for:
1._____
,2._____
3._____ Answer: Parking of vehicles
Building access or
Storage
R322.3.5 Enclosed areas below design flood elevation.
◉ Address number shall be a minimum of ___ inches high with a
minimum stroke of ____inch. Answer: 4 in.
1/2 in.
R319.1 Address numbers
◉ Protection of wood and wood based products from ___ shall be
provided by the use of naturally durable wood or wood that is
preservative treated. Answer: Decay
R317.1 Location required
◉ Dwelling Units in two-family dwellings shall be separated from
each other by wall and/or floor assemblies having not less than ___-
hour fire resistive rating. Answer: 1 hour
,R302.3 Two family dwellings
◉ In areas where the probability of termite infestation is "very
heavy", the clearance between foam plastics installed above grade
and exposed earth shall be at least ____ inches. Answer: 6 in.
R318.4 Foam plastic protection
◉ A thermal barrier is not required for foam plastic insulation in an
attic that is entered only for purposes of ____ or ____. Answer: Repairs
or maintenance
R316.5.3 Attics
◉ Foam plastic shall be separated from the interior of a building by
an approved ____ ____ of minimum ____- inch gypsum wallboard.
Answer: Thermal barrier
1/2 in.
R316.4 Thermal barrier
◉ All exterior footings shall be placed at least ___ inches below the
undisturbed ground surface. Answer: 12 in.
, (Where applicable, the dept of footings shall also conform to
R403.1.4.1 - R403.1.4.2)
R403.1.4 Minimum length
◉ The top surface of footings shall be level. The bottom surface of
footings shall not have a slope exceeding ____ unit vertical in ____
units horizontal. Answer: 1:10
R403.1.5 Slope
◉ Wood sill plates shall be anchored to the foundation with anchor
bolts spaced a maximum of ____ feet on center. Answer: 6 ft.
R403.1.6 Foundation anchorage
◉ Foundation anchor bolts shall be at least ___ inch in diameter and
shall extend a minimum of ___ inches into the concrete or grouted
cells of concrete masonry units. Answer: 1/2 in.
7 in.
R403.1.6 Foundation anchorage
◉ Isolated hollow masonry piers shall have a minimum nominal
thickness of ____ inches. Answer: 8 in.
BUILDING CERTIFICATION TEST
WITH ACCURATE ANSWERS
◉ In Seismic Design Categories Do, D1 and D2, foundations with
stem walls shall be provided with a minimum of one No. ___ bar
within 12 inches of the top of the wall and one No. ___ bar located 3
to 4 inches from the bottom of the footing. Answer: #4
#4
R403.1.3.1 Foundations with stemwalls
◉ The grade away from foundation walls shall fall a minimum of ___
inches within the first ____ feet. Answer: 6 in.
10 ft.
(Read exception)
R401.3 Drainage
◉ In flood hazard areas, enclosed areas below the design flood
elevation shall be used sole for:
1._____
,2._____
3._____ Answer: Parking of vehicles
Building access or
Storage
R322.3.5 Enclosed areas below design flood elevation.
◉ Address number shall be a minimum of ___ inches high with a
minimum stroke of ____inch. Answer: 4 in.
1/2 in.
R319.1 Address numbers
◉ Protection of wood and wood based products from ___ shall be
provided by the use of naturally durable wood or wood that is
preservative treated. Answer: Decay
R317.1 Location required
◉ Dwelling Units in two-family dwellings shall be separated from
each other by wall and/or floor assemblies having not less than ___-
hour fire resistive rating. Answer: 1 hour
,R302.3 Two family dwellings
◉ In areas where the probability of termite infestation is "very
heavy", the clearance between foam plastics installed above grade
and exposed earth shall be at least ____ inches. Answer: 6 in.
R318.4 Foam plastic protection
◉ A thermal barrier is not required for foam plastic insulation in an
attic that is entered only for purposes of ____ or ____. Answer: Repairs
or maintenance
R316.5.3 Attics
◉ Foam plastic shall be separated from the interior of a building by
an approved ____ ____ of minimum ____- inch gypsum wallboard.
Answer: Thermal barrier
1/2 in.
R316.4 Thermal barrier
◉ All exterior footings shall be placed at least ___ inches below the
undisturbed ground surface. Answer: 12 in.
, (Where applicable, the dept of footings shall also conform to
R403.1.4.1 - R403.1.4.2)
R403.1.4 Minimum length
◉ The top surface of footings shall be level. The bottom surface of
footings shall not have a slope exceeding ____ unit vertical in ____
units horizontal. Answer: 1:10
R403.1.5 Slope
◉ Wood sill plates shall be anchored to the foundation with anchor
bolts spaced a maximum of ____ feet on center. Answer: 6 ft.
R403.1.6 Foundation anchorage
◉ Foundation anchor bolts shall be at least ___ inch in diameter and
shall extend a minimum of ___ inches into the concrete or grouted
cells of concrete masonry units. Answer: 1/2 in.
7 in.
R403.1.6 Foundation anchorage
◉ Isolated hollow masonry piers shall have a minimum nominal
thickness of ____ inches. Answer: 8 in.