NETA III Exam Questions with
Complete Solutions28

The alternate source for emergency systems are required to be equipped with ground-fault
protection of equipment. - ANSWERS-False



Which ANSI/IEEE standard covers SF6 circuit breakers? - ANSWERS-C37.04



You measure the winding resistance of a 12.4kV, 1000kVA, Delta-Delta connected transformer
with a 100A test set. H1-H2 measures 42.0 microhms, H2-H3 measures 41.9 microhms, and H3-
H1 measures 84.0 microhms. What can you conclude from these readings? - ANSWERS-One
phase of the transformer is open.



When monitoring for entries involving a decent into atmospheres that may be stratisfied, the
envelope should be tested at a distance of approximately _____ feet in the direction of travel
and to each side. - ANSWERS-4



The transformer manufacturer should be consulted if winding-resistance test values vary by
more than _____ percent from factory test values or between adjacent phases according to
NETA acceptance testing standards. - ANSWERS-2



A DC shunt motor should never be operated: - ANSWERS-with the field circuit open



What is the expected torque (pound-feet) value of a 3/8" Grade 5 bolt? - ANSWERS-20



The generally accepted limits of deviation from the nominal 60Hz utility power frequency is: -
ANSWERS-.50Hz

,Power Factor testing is least effective on which of the following? - ANSWERS-MV Cable



Which of the following insulating liquid tests is optional when maintenance testing a 13.2kV-
4.16kV 1500kVA transformer with silicone fluid per NETA standards? - ANSWERS-ASTM D1298



Panelboards equipped with snap switches of rating 30 amps or less shall be provided with over-
current protection of not more than _____ . - ANSWERS-200 amps



Underground service conductors between the terminals of service equipment and service
lateral or underground service conductors are termed as _____ . - ANSWERS-Service Entrance
Conductors



What is a dual element fuse used for? - ANSWERS-Operate with a temporary overload



The full-load current for a single-phase alternating current 115 volt, 1 horsepower motor is
which of the following: - ANSWERS-16 A



Infrared surveys should be performed during periods of maximum possible loading but not less
than _____ % of rated load of the electrical equipment being inspected. - ANSWERS-40



Decreasing the opening time of the overcurrent protective device will decrease Arc-Flash
hazards. - ANSWERS-true



In a wye connected system, without neutral grounding, zero sequence currents are: - ANSWERS-
zero



When evaluating insulation test results on a medium-voltage, air-magnetic circuit breaker, what
quantity is evaluated? - ANSWERS-watts-loss

, In accordance with NETA and IEEE standards, the correct acceptance test voltage (dc) for 35KV
rated EPR 133% insulation level cable is? - ANSWERS-124kV



Calculate the circuit time constant of an inductor having resistance value of 100 ohms and an
inductance value of 4 Henry: - ANSWERS-0.04 sec

T=L/R



Transformer polarity: - ANSWERS-Is of concern when multiple sets of primary and secondary
windings are interconnected



Identify the least reliable power system arrangement: - ANSWERS-Radial w/ Primary Selectivity



The hot collar bushing test should be performed using which of the following test modes? -
ANSWERS-UST

GST

GST-g



R rated fuses are used for: - ANSWERS-Protection for motors

R-rated fuses provide required short-circuit protection for medium voltage motors, motor
controllers and associated circuitry. Relays provide both overload protection and locked rotor
protection to the motor.



Which of the following would be a factor in choosing between 100%, 133%, and 173% Medium
voltage cable for a power system? - ANSWERS-Ground Fault protection



During the performance of a thermographic scan of similar components within the switchboard
that are under similar load, at what temperature difference does NETA recommend
investigation? - ANSWERS-1-3 deg C

Información del documento

Subido en
3 de julio de 2026
Número de páginas
28
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$15.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
ETHANSMILE
4.1
(40)
Vendido
167
Seguidores
104
Artículos
2607
Última venta
1 semana hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes