The alternate source for emergency systems are required to be equipped with ground-fault
protection of equipment. - ANSWERS-False



Which ANSI/IEEE standard covers SF6 circuit breakers? - ANSWERS-C37.04



You measure the winding resistance of a 12.4kV, 1000kVA, Delta-Delta connected transformer
with a 100A test set. H1-H2 measures 42.0 microhms, H2-H3 measures 41.9 microhms, and H3-
H1 measures 84.0 microhms. What can you conclude from these readings? - ANSWERS-One
phase of the transformer is open.



When monitoring for entries involving a decent into atmospheres that may be stratisfied, the
envelope should be tested at a distance of approximately _____ feet in the direction of travel
and to each side. - ANSWERS-4



The transformer manufacturer should be consulted if winding-resistance test values vary by
more than _____ percent from factory test values or between adjacent phases according to
NETA acceptance testing standards. - ANSWERS-2



A DC shunt motor should never be operated: - ANSWERS-with the field circuit open



What is the expected torque (pound-feet) value of a 3/8" Grade 5 bolt? - ANSWERS-20



The generally accepted limits of deviation from the nominal 60Hz utility power frequency is: -
ANSWERS-.50Hz

,Power Factor testing is least effective on which of the following? - ANSWERS-MV Cable



Which of the following insulating liquid tests is optional when maintenance testing a 13.2kV-
4.16kV 1500kVA transformer with silicone fluid per NETA standards? - ANSWERS-ASTM D1298



Panelboards equipped with snap switches of rating 30 amps or less shall be provided with over-
current protection of not more than _____ . - ANSWERS-200 amps



Underground service conductors between the terminals of service equipment and service
lateral or underground service conductors are termed as _____ . - ANSWERS-Service Entrance
Conductors



What is a dual element fuse used for? - ANSWERS-Operate with a temporary overload



The full-load current for a single-phase alternating current 115 volt, 1 horsepower motor is
which of the following: - ANSWERS-16 A



Infrared surveys should be performed during periods of maximum possible loading but not less
than _____ % of rated load of the electrical equipment being inspected. - ANSWERS-40



Decreasing the opening time of the overcurrent protective device will decrease Arc-Flash
hazards. - ANSWERS-true



In a wye connected system, without neutral grounding, zero sequence currents are: - ANSWERS-
zero



When evaluating insulation test results on a medium-voltage, air-magnetic circuit breaker, what
quantity is evaluated? - ANSWERS-watts-loss

, In accordance with NETA and IEEE standards, the correct acceptance test voltage (dc) for 35KV
rated EPR 133% insulation level cable is? - ANSWERS-124kV



Calculate the circuit time constant of an inductor having resistance value of 100 ohms and an
inductance value of 4 Henry: - ANSWERS-0.04 sec

T=L/R



Transformer polarity: - ANSWERS-Is of concern when multiple sets of primary and secondary
windings are interconnected



Identify the least reliable power system arrangement: - ANSWERS-Radial w/ Primary Selectivity



The hot collar bushing test should be performed using which of the following test modes? -
ANSWERS-UST

GST

GST-g



R rated fuses are used for: - ANSWERS-Protection for motors

R-rated fuses provide required short-circuit protection for medium voltage motors, motor
controllers and associated circuitry. Relays provide both overload protection and locked rotor
protection to the motor.



Which of the following would be a factor in choosing between 100%, 133%, and 173% Medium
voltage cable for a power system? - ANSWERS-Ground Fault protection



During the performance of a thermographic scan of similar components within the switchboard
that are under similar load, at what temperature difference does NETA recommend
investigation? - ANSWERS-1-3 deg C

Document information

Uploaded on
July 3, 2026
Number of pages
28
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers
$15.99

Wrong document? Swap it for free Within 14 days of purchase and before downloading, you can choose a different document. You can simply spend the amount again.
Written by students who passed
Immediately available after payment
Read online or as PDF

Seller avatar
Reputation scores are based on the amount of documents a seller has sold for a fee and the reviews they have received for those documents. There are three levels: Bronze, Silver and Gold. The better the reputation, the more your can rely on the quality of the sellers work.
ETHANSMILE
4.1
(40)
Sold
165
Followers
104
Items
2603
Last sold
1 week ago


Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their exams and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can immediately select a different document that better matches what you need.

Pay how you prefer, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card or EFT and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Working on your references?

Create accurate citations in APA, MLA and Harvard with our free citation generator.

Working on your references?

Frequently asked questions