what is the difference between check valve 1 and check valve 2 on a double check valve assembly - ANSWERthe two check valves operate the same in a perfect vacuum, water can be drawn up in a column _______ feet - ANSWER33.9

Vista previa del contenido

BACK FLOW TEST PRACTICE TEST
CORRECT 100%
what is the difference between check valve 1 and check valve 2 on a double check
valve assembly - ANSWERthe two check valves operate the same

in a perfect vacuum, water can be drawn up in a column _______ feet - ANSWER33.9

which of the following is considered to be a chemical contaminant? - ANSWERarsenic

which of the following is considered to be a biological health hazard - ANSWERgiardia

what type of assembly has two internally spring loaded check, two shut-off valves, and
four test cocks? - ANSWERdouble check valve

air gap is the_________ when directly connecting potable water supply lines to
sewerage systems or to radioactive sources? - ANSWERmost suitable protection

a bypass of a backflow prevention assemble may be permitted only if the assembly in
the bypass: - ANSWERis the same type

what federal law made water purveyors responsible for water quality all the way into
consumers' homes or businesses? - ANSWERsafe drinking water act amendment of
1986

if a column of water is exerting a pressure of 50 psi, how high must the water be inside
the column? - ANSWER115.5

as the velocity of water increases, pressure: - ANSWERdecreases

atmospheric pressure at sea level is _______ psi - ANSWER14.7

a water supply other than the water purveyor's approved supply, that is on or available
to the premises is called a - ANSWERauxiliary water supply

how can a backsiphonage action be broken - ANSWERair gap

what single difficult to regulate item is most commonly associated with cross
connections, specifically through backsiphonage? - ANSWERgarden house

the appropriate height fo an air gap is - ANSWERtwice the diameter of the pipe above
the flood rim of vessel, minimum of 1 inch

, while testing check balbe #1 on a DC, water recedes from the tuve attached to test cock
#3. The gauge should be moved to the centerline of the assembly and the static
pressure drop across the no. 1 check should be recorded. What other information
should be recorded. - ANSWERcheck valve #2 is leaking and shutoff valve #2 is leaking

at what point is the relief valve in an RP required to open - ANSWER2.0 psid

what is the minimum spring tension recommended on the #1 check valve in an RPZ -
ANSWER3 psi greater than the tension on the relief valve.

according to the USC, what is the correct height for installing an RPZ - ANSWER12
inches above grade, but no more than 36 inches

what is the correct height to install a PVB - ANSWER12 inches above the highest
downstream point.

what company or agency is responsible for testing and approving all backflow
prevention assemblies in the united states? - ANSWERfoundation of cross-connection
control & hydraulic research

backflow prevention assemblies are often installed in parallel in order to: -
ANSWERmaintain service during testing and repairs

which of the following is not a criterion for an approved assembly? - ANSWERshipped
by manufacturer in separate parts for inspection

what is the minimum pressure drop across a spring-loaded, soft-seated check valve? -
ANSWER1.0 psid

when testing a double check valve assembly, what is the correct order for closing the
shutoff valves? - ANSWERshutoff #2 , then shutoff #1

where is the relief valve of an RPZ located? - ANSWERbetween check valve #1 and
check valve #2

an atmospheric vacuum breaker is designed to protect against? - ANSWERPollutants &
contaminants, but under backsiphonage only

backflow prevention by containment means: - ANSWERplacing a backflow preventer at
the meter

what type of backflow prevention assembly would be recommended in a car wash
facility at the service connection to a potable water supply? - ANSWERRPZ

Información del documento

Subido en
12 de febrero de 2026
Número de páginas
5
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$12.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
shantelleG
4.0
(118)
Vendido
650
Seguidores
369
Artículos
18317
Última venta
2 días hace



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes