What is a general requirement of the location of the
installation of a boiler? - Answer-Adequate clearance from
combustile construction
What temperature must the materials remain under during
combustion? - Answer-170 degrees
What is a requirement for the access of the boiler? -
Answer-Access for operation and maintenance must not
be hazardous
What is required upon installation to operate a boiler? -
Answer-Inspection and test resulting in equipment use
permit from commissioner
How often should a boiler be inspected? - Answer-Once a
year
,2|Page
What documentation is required from a certificate holder?
- Answer-Owners annual statement
What is required to hydrostatically test upon installation
and who should perform these tests? - Answer-Liquid fuel
piping and fuel oil storage tanks by the installing contractor
At what pressure should piping be tested? - Answer-1/2
max working pressure but less than pressure required for
storage tank
All heating, combustion, and cooking equipment shall be
provided with insulation or the building construction shall
be fire protected, so that during operation the surface of
combustible construction materials will not be raised to a
temperature higher than ____. - Answer-170 ̊ F
Acceptance tests: Boilers shall not be placed in operation
upon completion of construction until they have been ____
and an equipment use permit has been issued by the
commissioner. - Answer-Inspected and tested.
Periodic boiler inspections: All boilers shall be inspected at
least ____ including chimney connections. - Answer-Once
a year.
,3|Page
Owner's annual statement: The owner of each boiler that
is subject to periodic inspections shall file an annual ____
with the commissioner, specifying the location of each
boiler and arrangement for inspection. - Answer-Written
statement.
What three things must be tested for any fuel burning and
storage installation before the system can be operated? -
Answer-(1) Tightness of liquid fuel piping.
(2) Tightness of fuel oil storage tanks.
(3) Tightness of gas distribution piping.
What are instruction cards for oil burning systems? -
Answer-Cards giving complete instructions for care and
operation that are permanently located near the
equipment.
Every oil burning installation that is not fully automatic or
requires preheating shall be operated by, or under, the
, 4|Page
direct supervision of a person holding a ____ issued by
the fire commissioner. - Answer-COF
After any fuel burning equipment repair for which a
licensed operator is required, such operator shall also
check the repairs and be ____ while the equipment is
started. - Answer-Present.
What is abatement of air contaminants? - Answer-
Compliance with the air pollution control code.
What are the 3 equipment classifications and their
temperatures for the products of combustion at the point of
leaving the equipment? - Answer-(1) Low Temp: 600° F or
less.
(2) Medium Temp: 600° - 1000° F.
(3) High Temp: 1000° or greater.
Ventilation shall be capable of providing at least ____
CFM of air for each gallon of oil per hour required to fire
the equipment to gross output. - Answer-36