Escrito por estudiantes que aprobaron Inmediatamente disponible después del pago Leer en línea o como PDF ¿Documento equivocado? Cámbialo gratis 4,6 TrustPilot
logo-home
Document preview thumbnail
Vista previa 3 fuera de 45 páginas
Examen

2026 Latest EVITP Exam FINAL Prep – 130 Questions with Correct Detailed -Answer- s | Electric Vehicle Installation Training Program Certification

Document preview thumbnail
Vista previa 3 fuera de 45 páginas

2026 Latest EVITP Exam FINAL Prep – 130 Questions with Correct Detailed -Answer- s | Electric Vehicle Installation Training Program Certification

Vista previa del contenido

2026 Latest EVITP Exam FINAL Prep – 130 Questions
with Correct Detailed -Answer- s | Electric Vehicle
Installation Training Program Certification




EVITP Final Exam Practice Questions (1-10)
1. According to NEC Article 625, the conductors supplying Electric Vehicle Supply
Equipment (EVSE) must have an ampacity of at least what percentage of the
EVSE's maximum load?
A) 100%
B) 115%
C) 125%
D) 150%
-Answer- : C) 125%
Explanation: NEC 625.41 states that EVSE shall be considered a continuous load
for branch circuit and feeder calculations. Per the definition of a continuous load
(NEC Article 100) and requirements in 210.19(A)(1)(a), conductors must be sized
at 125% of the continuous load. This is one of the most fundamental and
frequently tested rules in EVITP.


2. When installing a Level 2 EVSE on a dedicated 40-amp circuit in a new
dwelling unit garage, what is the MINIMUM size THHN copper conductor
required in the raceway?
A) 8 AWG
B) 6 AWG
C) 4 AWG
D) 10 AWG
-Answer- : A) 8 AWG
*Explanation: A 40-amp circuit requires conductors sized for 125% of the load:

,40A x 1.25 = 50A. Referring to NEC Table 310.16, an 8 AWG copper conductor at
75°C (common termination rating) has an ampacity of 50A. 10 AWG is only rated
for 35A, and 6 AWG (65A) would be larger than the minimum required.*


3. A commercial installation plans for ten (10) identical Level 2 EVSE units. Each
unit has a nameplate rating of 32 amps at 208V. Using the demand factors in
Table 625.42, what is the calculated load for the feeder supplying all ten units?
A) 256 amps
B) 320 amps
C) 200 amps
D) 192 amps
-Answer- : D) 192 amps
*Explanation: First, the continuous load per unit is 32A x 1.25 = 40A. For 10 units,
the total connected load is 10 x 40A = 400A. Now apply the demand factor from
NEC Table 625.42 (not provided here but a must-know). For 10 units, the demand
factor is 48%. Therefore, 400A x 0.48 = 192A. This tests your ability to apply both
the continuous load rule AND the commercial demand factors correctly.*


4. Which of the following is NOT a required characteristic of an EV coupler
(connector) as specified in NEC 625.13?
A) It must be listed for the purpose.
B) It must be polarized.
C) It must have a "dead-front" design (no exposed pins when disconnected).
D) It must be capable of being locked in the connected position.
-Answer- : D) It must be capable of being locked in the connected position.
*Explanation: NEC 625.13(A) requires couplers to be listed, polarized, and have a
dead-front design. While some connectors may have a locking feature, it is not a
code-mandated characteristic. This is a classic "EXCEPT" question—read carefully.
Locking the disconnecting means is required, not necessarily the connector
itself.*

, 5. An EVSE is installed outdoors in a parking lot and is subject to physical
damage from vehicles. According to the NEC, what protective measure is
required?
A) Installation in an underground vault.
B) Guard posts or curbs meeting specific strength and location requirements.
C) A dedicated concrete island with warning signage.
D) Relocation to an area not subject to damage.
-Answer- : B) Guard posts or curbs meeting specific strength and location
requirements.
Explanation: NEC 625.42 specifically addresses overhead protection. Where
subject to severe physical damage, EVSE must be protected by guard posts or
similar means. The code references other sections (e.g., 110.27(B)) for specifics on
the construction of these guards. This is a direct code application question.


6. A PSW is installing EVSE in a public garage. The disconnecting means for the
EVSE must be:
A) Integral to the EVSE unit.
B) Within sight of and readily accessible to the EVSE.
C) Located at the main service panel only.
D) A Type HS fuse disconnect.
-Answer- : B) Within sight of and readily accessible to the EVSE.
Explanation: NEC 625.18 is clear: a disconnecting means for all ungrounded
conductors must be provided and shall be within sight of and readily accessible to
the EVSE. If not within sight, it must be capable of being locked in the open
position. Integral disconnects may satisfy this if they meet the definition.


7. What is the primary personnel protection system required for all receptacles
installed for EV charging?
A) An Equipment Grounding Conductor (EGC) sized per Table 250.122.
B) A Ground-Fault Circuit Interrupter (GFCI) of the Class A type.
C) An Isolation Transformer.
D) An Arc-Fault Circuit Interrupter (AFCI).

Información del documento

Subido en
5 de febrero de 2026
Número de páginas
45
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$23.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
NursingTotur2
3.3
(78)
Vendido
532
Seguidores
36
Artículos
5943
Última venta
8 horas hace


Reseñas de compradores verificados

5 meses hace

Thank you so much for the 5-star rating! I truly appreciate your support and feedback — it means a lot. If you’d like to see more high-quality nursing resources and updates, feel free to follow Nursing Tutor 2 here: https://www.stuvia.com/user/NursingTotur2 Thanks again, and wishing you all the best in your studies! .



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes