A listed assembly of two , three, or four insulated circuit
conductors within a NONMETALLIC jacket, an extruded
thermoplastic covering, or a sealed nonmetallic covering that can
be mounted directly on the surface of walls and ceilings is the
definition for:
A) Flat conductor cable
B) Flat cable assemblies
C) Nonmetallic sheath cable
D) Concealable nonmetallic extension - ANSWER-Concealable
nonmetallic extension
(article 382.2)
A group of devices that serve to govern in some predetermined
manner the electric power delivered to the apparatus to which it is
connected is a ?
,2|Page
A) Device
B) Controller
C) Disconnect
D) Circuit breaker - ANSWER-Controller
(article 100)
For a service panel fed by parallel 3/0 AWG copper conductors,
the copper GROUNDING - ELECTRODE run from the service
panel to the metallic water service shall be at least size
____________ AWG
A) 4
B) 2
C) 1/0
D) 2/0 - ANSWER-2
(table 250.66)
,3|Page
A dry - type TRANSFORMER may be LOCATED in a suspended
ceiling space where it is not ready ACCESSIBLE if the voltage is
600 volts or less and has a maximum rating of ____________ kva
A) 10
B) 25
C) 50
D( 112 - ANSWER-50
(article 450.13 (B) )
A SERVICE head can be located no further away from the point of
attachment than ____________ inches
A) 18
B) 24
C) 36
D) 48 - ANSWER-24"
, 4|Page
(article 230.54) (C) (exceptions)
ACCEPTABLE METHODS of connecting GROUNDING and
BONDING conductors include all the following, EXCEPT:
A) Solder joints
B) Terminal bars
C) Exothermic weld
D) Listed pressure connectors - ANSWER-solder joints
(article 250.8 (A)
The amount of available fault current at the service depends upon
the :
A) Method of bonding
B) Method of grounding