1. There are six conductors in a race way connected to 75° C rated circuit
breaker. Each wire has a 70 amp load using THHM conductors. The
minimum size conductors used our #_________AWG - ANSWER ✔ 4
2. Thermal insulation shall not be installed within _________inches of
recessed lighting fixtures - ANSWER ✔ 3
3. A 1 inch conduit contains three wire circuits or a phase system. All
conductors are number 10 TW. Each circuit consist of two phase conductors
and one grounding conductor and one equipment grounding conductor. The
maximum and pasty of each phase conductor is______. - ANSWER ✔ 24
amps
4. The volt Ampere rating of a device that consumes 14.5 A on a 240 V circuit
is_____. - ANSWER ✔ 3480watts
,5. A 208 V, three phase heater draws 3598 W . How many campers does the
heater draw - ANSWER ✔ 10
6. The underwater light fixture shall be installed at least ________inches below
the water level - ANSWER ✔ 18
7. A general purpose receptacle shall not be installed on the_________ -
ANSWER ✔ Offense directly south of the pool
8. A junction box for a 124 wet niche fixture shall be at least_______Inches
above the ground - ANSWER ✔ 4
9. A GFCI protected_______ receptacle for the pump motor May be installed
on the south side of the dwelling unit dedicated grounding type - ANSWER
✔ Dedicated receptacle
10.A metal fence installed within________Feet of a pool Shall be bonded -
ANSWER ✔ 5
11.The feed to the wet niche fixture shall be installed in - ANSWER ✔ Rigid
brass
12.A 15 or 20 amp receptacle Shall be located within_____Feet of a rooftop air
conditioner - ANSWER ✔ 25
,13.In a commercial building the minimum size ungrounded service entrance
conductor for 120 Dash 240 V single phase 200 amp service is - ANSWER
✔ 3/0 thwn copper
14.The minimum service for a one family dwelling Shall be - ANSWER ✔
100amps
1. Where PV system DC circuits are run inside a building, they shall be
contained in metal raceways,____ or metal enclosures from the point of
penetration of the surface of the building to the readily accessible
disconnecting means. - ANSWER ✔ Type MC cable 690.31.G
2. Unless specifically listed and marked for the location, the coupling means of
the electric vehicle supply equipment shall be stored or located at a height of
not less than___ inches above the grade level for outdoor locations. -
ANSWER ✔ 24' 625.50
3. Unless specifically listed and marked for the location, the coupling means of
the electric vehicle supply equipment shall be stored or located at a height of
not less than___ inches above the floor level for indoor locations. -
ANSWER ✔ 18" 625.50
4. All 15 and 20 ampere, 125 volt non locking type receptacles installed in the
vehicle washing area of a carwash shall be listed and so identified as___
type. - ANSWER ✔ weather resistant 406.9.B1
, 5. All 15 and 20 ampere, 125 volt non locking type receptacles installed in the
vehicle washing area of a carwash shall have an enclosure that is____
whether or not the attachment plug cap is inserted - ANSWER ✔ weather
proof 406.9.B
6. An individual, other than an individual who is licensed under this article
and___ and working under the direction of a holder of an electrical
contractor's license, shall not in any manner undertake to execute any
electrical wiring. - ANSWER ✔ employed by PA.407 339.5737
7. The ratio of electrical journeyman or master electricians to registered
apprentice electricians shall be on the basis of___ electrical journeyman or
master electricians to no more than___ registered apprentice electricians. -
ANSWER ✔ 1 to 3 PA.407 339.5717 sec 717.3
8. Who can obtain a sign specialty contractor's license? - ANSWER ✔ an
individual whom holds a sign specialist license
9. Where fuses rated___ amperes or higher are installed, the fuse shall have a
clearing time of 0.07 seconds or less at the available arcing current. -
ANSWER ✔ 1200amps 240.67.B
10.A meeting room that is at least 12 feet wide and has a floor area of at least
215 square feet shall have at least___ receptacle outlet(s) located in the floor
at a distance not less than 6 feet from any fixed wall for each 215 square feet
or major portion of floor space. - ANSWER ✔ 1 210.71.B2