Questions & Certified Solutions |
Complete Accurate Quizzes with
Verified Answers, 2025-2026
Terms in this set (344)
_____________Quiz____________?
Sprinkler System -
Answer✓✓
A fire extinguishing system, other than a water mist system, that utilizes water as the
extinguishing agent.
_____________Quiz____________?
Automatic/Non-Automatic Sprinkler Systems -
Answer✓✓
Shall be inspected by a competent person holding a S12 CoF and employed or contracted by
the owner, to see that all parts of the system are in good working order, and that the fire
department connections, if any, are ready for immediate use by the fire department.
_____________Quiz____________?
6 Extra Sprinkler Heads -
1
, Answer✓✓
A Supply of ____ shall be kept available on the premises, to replace promptly any fused or
damaged_____
_____________Quiz____________?
Fire Department Connections/Connections for a Sprinkler System -
Answer✓✓
Subjected to a hydrostatic pressure test to demonstrate its suitability for fire department use,
every 5 years.
_____________Quiz____________?
Impairment Coordinator -
Answer✓✓
Complies with the requirements of study material
_____________Quiz____________?
Impairment Coordinator -
Answer✓✓
Shall take the actions when a standpipe system, sprinkler system or the fire alarm system is out
of service.
_____________Quiz____________?
Impairment Coordinator -
2
, Answer✓✓
Shall maintain records of all system inspections, tests, servicing and other items of maintenance.
_____________Quiz____________?
Impairment Coordinator -
Answer✓✓
Building Owner in the absence of a specific designee.
_____________Quiz____________?
Planned Removal From Service -
Answer✓✓
When the system, or a portion of the sprinkler system, is placed out of service for a scheduled
inspection, testing, regular maintenance, minor repairs or for construction affecting not more
than 1 floor.
_____________Quiz____________?
Unplanned Out of Service Condition -
Answer✓✓
A serious defect in the sprinkler system including, but not limited to: an empty tank, a break or
major leak in the system's water piping, inoperative or shut water supply valves, defective fire
department connections, construction related shut downs affecting more than one floor, or
complete or partial shut downs of the sprinkler system, other than a shut down for a planned
removal form service.
3
, _____________Quiz____________?
Tag Requirement -
Answer✓✓
Shall be used to indicate that a system, or portions are out of service.
_____________Quiz____________?
Tags -
Answer✓✓
Shall indicate the are affected, a brief description of the condition, the occupancy classification,
CoF number and the estimated time until the system becomes operational.
_____________Quiz____________?
Green Tags -
Answer✓✓
If no impairment is found in the entire system ___ will be placed on the main control valve.
_____________Quiz____________?
Systems Fully Out of Service -
Answer✓✓
White Discs 8-9" in diameter is placed on all affected fire department connections. A red tag
shall be placed at the main control valve indicating the sprinkler company name, date of removal
from service and anticipated return to service date.
4