Journeyman Electrician Practice Test | 2023 | 50 Questions with 100% Correct Answers | Updated & Verified
Conductors with _____ marked on the insulation are NOT approved for use in a wet location. - THHN conductors with THHN insulation are approved for use in dry and damp locations only and conductors with THWN, THHW, and THW insulation are recognized for use in dry and wet locations. Given: A one-family dwelling unit with a demand load of 200 amperes is supplied with a 120/240 volt, single-phase, electrical system from the local utility company. What is the MINIMUM size aluminum THW conductors required for use as service-entrance conductors for this residence? - 4/0 AWG one-family dwelling 120/240 volt, single-phase, service-entrance conductors to be sized at an ampacity of not less than 83% of the service rating. Therefore, 200 amperes x 83% = 166 amperes; size 4/0 AWG THW aluminum conductors with an allowable ampacity of 180 amperes should be selected for this dwelling. Where a 150 kVA, single-phase transformer having a secondary voltage of 120/240 is installed at a multi-family dwelling, the full-load current rating, in amperes, of the secondary is _____. - 625 amperes