After the testing and reinstallation of plugs and caps for
auxiliary drain and test valves, what action is required? - THE
CORRECT ANSWER-Shall be restored to full operational condition,
To avoid false alarms where a supervisory service is provided
the alarm receiving facility shall be notified by the property
owner or designated representative before? - THE CORRECT ANSWER-
conducting any test or procedure that could result in the
activation of an alarm,
Sprinklers shall be inspected when and how? - THE CORRECT
ANSWER-Shall be inspected from the floor level annually
Sprinklers shall not show signs of the following? - THE CORRECT
ANSWER-leakage; shall be free of corrosion, foreign materials,
paint, and physical damage; and shall be installed in the correct
orientation
, Sprinklers installed installed in concealed spaces such as above
ceilings shall what? - THE CORRECT ANSWER-Shall not require
inspection,
Sprinklers installed in areas that are inaccessible for safety
considerations due to process operations shall be inspected? -
THE CORRECT ANSWER-During each scheduled shutdown
The supply of spare sprinklers shall be inspected when? - THE
CORRECT ANSWER-Annually,
A spare sprinkler wrench shall be required for what? - THE
CORRECT ANSWER-Every type of sprinkler,
Sprinkler pipe and fittings shall be inspected from where and
when? - THE CORRECT ANSWER-Annually from from the floor level,
Sprinkler Pipe hangers and seismic bracing shall be inspected? -
THE CORRECT ANSWER-Annually from the floor level
Gauges on a wet pipe sprinkler system shall be inspected? - THE
CORRECT ANSWER-Monthly,
Gauges on a dry, preaction system, and deluge systems shall be
inspected? - THE CORRECT ANSWER-Monthly
When the gauge near the compressor is reading higher than the
gauge near the dry pipe valve, the air line shall be what? - THE
CORRECT ANSWER-Taken out of service