NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES NEWEST VERSION 2025/2026 ACTUAL QUESTION AND CORRECT DETAILED VERIFIED ANSWERS FROM VERIFIED SOURCES RATED A GRADE.

Puntuación
4.0
(1)
Vendido
-
Páginas
24
Grado
A+
Subido en
03-02-2025
Escrito en
2024/2025

NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES NEWEST VERSION 2025/2026 ACTUAL QUESTION AND CORRECT DETAILED VERIFIED ANSWERS FROM VERIFIED SOURCES RATED A GRADE.

Institución
NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES
Grado
NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES










Ups! No podemos cargar tu documento ahora. Inténtalo de nuevo o contacta con soporte.

Escuela, estudio y materia

Institución
NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES
Grado
NCCER 26401 LOAD CALCULATIONS-FEEDER AND SERVICES

Información del documento

Subido en
3 de febrero de 2025
Número de páginas
24
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas

Temas

Vista previa del contenido

NCCER 26401 LOAD CALCULATIONS-FEEDER
AND SERVICES NEWEST VERSION 2025/2026
ACTUAL QUESTION AND CORRECT DETAILED
VERIFIED ANSWERS FROM VERIFIED SOURCES
RATED A GRADE.

Save




Terms in this set (113)


What is the minimum NEC 220.43 (A) Show windows 30ft x 200va = 6000 va
demand required for the
portion of a feeder that
supplies 30ft of show
window?

Residential Small apliance 1500 va
circuits must be rated at
__________ per NEC 220.52(A)

When performing load 60 amps
calculations for farm
buildings the load that
must be included in the
calculation at 100%
demand must be at least
_______ .

The demand lighting load 220. 14(M) 1.7 volt amperes per square foot. 18,000 va
for a 20,000 square foot
motel with no dining room
or ballroom is ____ per NEC
220.12 and 220.42

,What is the demand 72,000 va
lighting load for a 100,000
square foot hotel with no
dining room or ballroom is
____ per 220.12 and 220.42 ?

When calculating the Determine the sum of all the motor loads plus 25% of
feeder load for a motor the largest motor.
Control Center supplying
several Motors per 430.24
you must ______ .

A commercial kitchen with 65% demand factor
six or more pieces of
kitchen equipment is
subject to a demand
factor of ___________ per NEC
table 220.56.

When the overcurrent protection for a conductor is
What is a tap conductor? located on the load side rather than the supply side
of a conductor, it is considered to be a tap conductor

What is the minimum 3va per s.f.
general lighting load in
volt-amps per square foot
required by the NEC table
220.12 for a store?

•120a x 50ft = 6000
What is the total load
•110a x 60ft = 6600
center length for a tapped
•75a x 90ft = 6750
feeder with loads of 120a
•70a x 150ft = 10,500
at 50 feet, 110a at 60 feet,
•6000+6600+6750+10,500 = 29,850
75a and 90 feet, and 70
•120a+110a+75a+70a = 375a
amps at 150 feet?
•29,a = 79.6 ft load center length

, The minimum ampacity for •Table 555.12
a feeder supplying ten •9-14 receptacles @ 80%
30a shore power •10 receptacles x 30a = 300a
receptacles in a marina is •Apply the demand factor from 555.12 300a x 80% =
_____ per NEC table 555.12 240a

The minimum ampacity for •Table 555.12
a feeder supplying (30) •15-30 receptacles @ 70%
shore power receptacles •30 receptacles x 30a = 900a
in a marina each rated at •Apply the demand factor from 555.12 900a x 70% =
30a is _____ per NEC table 630a
555.12.

•What is the total load for •Use Table 430.250
a feeder serving •7.5 amps x 4 = 30a
•(4) 2 horsepower motors •16.7amps x 3 = 50.1a
7.5a • 46.2 amps x 1= 46.2a
•(3) 5 horsepower • 74.8 amps x 100% = 74.8
Motors16.7a •74.8a x .25% = 18.7a (add
•(1) 15 horsepower 46.2a additional 25% for largest motor
motor load)
•(1) 25 horsepower motor •30+50.1+46.2+74.8+18.7=219.8a or
? 74.8a 30+50.1+46.2+93.5 = 219.8a
•(all Motors are 208 volts)

What is the feeder •84,563 va / 208volts = 406.5522
ampacity for a three •Don’t forget it’s three phase! = 1.732
phase, 120/208 Volt •406..732 = 234.89a
subpanel with a
connected load of 84,563
Volt amps?

Using the Volt amps per •200va x 50ft = 10,000va
linear foot method, the •“Total” means include Continuous load
total Volt amps that must • 10,000va x 1.25 = 12,500va
be used in a service
calculation for a 50 foot
show window is ____ per
NEC 220.43(A).
$17.99
Accede al documento completo:

100% de satisfacción garantizada
Inmediatamente disponible después del pago
Tanto en línea como en PDF
No estas atado a nada

Reseñas de compradores verificados

Se muestran los comentarios
9 meses hace

4.0

1 reseñas

5
0
4
1
3
0
2
0
1
0
Reseñas confiables sobre Stuvia

Todas las reseñas las realizan usuarios reales de Stuvia después de compras verificadas.

Conoce al vendedor

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
Drvivek Johns Hopkins University School Of Nursing
Seguir Necesitas iniciar sesión para seguir a otros usuarios o asignaturas
Vendido
196
Miembro desde
1 año
Número de seguidores
1
Documentos
191
Última venta
3 días hace

4.5

229 reseñas

5
147
4
49
3
25
2
7
1
1

Recientemente visto por ti

Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes