Testing a valve supervisory s/w, a signal shall indicate
movement from the control valves normal
position during either the first ____ revolutions or
when the stem has moved 1/5th of the distance from its
normal position - ....ANSWER...2
Control valve supervisory s/w shall be tested _____ -
....ANSWER...Annually
Mechanical waterflow alarm devices shall be tested
_____ - ....ANSWER...Quarterly
System demand for class 2 standpipes shall be
based on _____ - ....ANSWER...standards at the time
of installation
1
,A semi-auto dry standpipe without a backflow
preventer shall have a main drain test _____ -
....ANSWER...Annually
A small leak inside a stairwell during a hydrostatic test
on a manual standpipe is a _____ -
....ANSWER...Non-Critical deficiency
2
, Air pressure supervision at a constantly manned
location, gauges are inspected _____ -
....ANSWER...Quarterly
A 5% degradation in the water supply during a main
drain test on an automatic wet standpipe, is
considered a _____ - ....ANSWER...Impairment
Automatic and Manual standpipes require a 5 year full
flow test. - ....ANSWER...False
When performing a hydrostatic test and inspecting the
standpipe, there is a hose rack that only swings
out 60 degrees. This is a _____ - ....ANSWER...Non-
Critical deficiency
When water damage is a concern, performing an air
test at _____ PSI is recommended before putting
water on the system - ....ANSWER...25
A pressure loss of 5 PSI is acceptable during a 5 yr
hydrostatic test. - ....ANSWER...False