NYC MASTER ELECTRICIAN EXAM WITH
CORRECT ANSWERS 2025/2026
Type ____ is multiconductor cable identified for use as underground service entrance cable. -
v v v v v v v v v v v v v
correct-answers-Type USE cable
v v v
Knife switch rated for more than 1200 Amps at 250Volts or less - correct-answers-
v v v v v v v v v v v v v
Can be used only as isolating switch, shall not be opened under load
v v v v v v v v v v v v
Track lighting with outlets in a bathroom is not allowed because ? - correct-answers-
v v v v v v v v v v v v v
Track lighting has receptacle
v v v
Where internal combustion engines are used as the prime motor, an on site fuel supply shall be provi
v v v v v v v v v v v v v v v v v
ded with an on premise fuel supply sufficient for not less than ____ hours full demand operation of t
v v v v v v v v v v v v v v v v v v
he system - correct-answers-6 hours
v v v v
Fixed in place X- v v v
ray equipment properly supplied by a branch circuit rated at not over ____ amperes shall be permitt
v v v v v v v v v v v v v v v v
ed to be supplied through a suitable attachment plug cap and hard service cable cord. - correct-
v v v v v v v v v v v v v v v v
answers-30 Amps v
Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - correct-answers-
v v v v v v v v v v v v v
Both ends v
,GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the ____ty
v v v v v v v v v v v v v v v v v v
pe. - correct-answers-Locking
v v
The maximum voltage drop from service point to the last over-current device in a dwelling unit? -
v v v v v v v v v v v v v v v v
correct-answers-4%
v
Which of the following statements best describe the grounding requirement for central vacuum out
v v v v v v v v v v v v v
let - correct-answers-
v v
Accessible non current carrying metal parts are required to be connected to an equipment groundin
v v v v v v v v v v v v v v
g conductor.
v
In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by at l
v v v v v v v v v v v v v v v v
east two branch circuits, which ____permitted to originate from two separate transfer switches on t
v v v v v v v v v v v v v v
he emergency system - correct-answers-Are permitted
v v v v v
Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges ,day
v v v v v v v v v v v v v v v
rooms, or similar areas - correct-answers-Do not include
v v v v v v v
The patient care area is any portion of the healthcare facility where patients are intended to be ____
v v v v v v v v v v v v v v v v v
or ____. - correct-answers-Examined or treated
v v v v v
Each general care area patient bed location in a healthcare facility must be provided with four ____ o
v v v v v v v v v v v v v v v v v
r ____ duplex receptacles - correct-answers-Single or two
v v v v v v v
A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical, care o
v v v v v v v v v v v v v v v v
n a 24 hour basis of ____ or more patients - correct-answers-Four
v v v v v v v v v v v
Where installed to reduce electrical noise for electronic equipment, electrical continuity of the met
v v v v v v v v v v v v v
al raceways shall not be required and metal raceway can terminate a (an) ____ nonmetallic fitting or
v v v v v v v v v v v v v v v v v
spacer on electronic equipment - correct-answers-Listed fitting
v v v v v v
,Feeder and branch circuit conductors within ____ inches of a Ballast shall have an insulation temper
v v v v v v v v v v v v v v v
ature rating not lower than 90°C (194°F) unless supplying a luminaiere marked as suitable for a differ
v v v v v v v v v v v v v v v v
ent insulation temperature - correct-answers-3 inches
v v v v v
Manufactured wiring systems constructed with type MC cable shall be supported and secured at int
v v v v v v v v v v v v v v
ervals not exceeding ____ ft. - correct-answers-6 ft
v v v v v v v
Where a main bonding jumper or a system bonding jumper is a screw only the screw shall be identifi
v v v v v v v v v v v v v v v v v v
ed with a ____ that shall be visible with the screw installed - correct-answers-Green finish
v v v v v v v v v v v v v v
Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the window, c
v v v v v v v v v v v v v v v v v v
ap, or other prominent part to distinguish them from fuses of higher ampere rating - correct-
v v v v v v v v v v v v v v v
answers-Hexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts (volt-
v v v v v v v v v v v v v v v v
amperes) or the nameplate rating, which ever is larger, for each dryer served ? - correct-answers-
v v v v v v v v v v v v v v v
5000 watts v
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of
v v v v v v v v v v v v v
____ windows that are designed to be opened, doors, porches, stairs fire escape or similar locations.
v v v v v v v v v v v v v v v
- correct-answers-3 ft (36 inches)
v v v v v
——
Cartridge fuses of the renewable type shall be permitted to be used only for replacement in existing
v v v v v v v v v v v v v v v v v v
installation is where there is no evidence of over-fusing or tampering. - correct-answers-Class H
v v v v v v v v v v v v v
Branch circuit conductors within ____inches of the ballast shall have an insulation temperature rati
v v v v v v v v v v v v v
ng not lower it 90°C 194°F - correct-answers-3" inches
v v v v v v v v
, The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - correct-answers-8
v v v v v v v v v v v v v v v v
In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground plug ? -
v v v v v v v v v v v v v v v v v v
correct-answers-Combination range hood/microwave oven
v v v v
Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent devic
v v v v v v v v v v v v v v v v v
e up to the equipment served.if ____ the type 3 SPD connection must be a minimum 30'ft of conduct
v v v v v v v v v v v v v v v v v v
or a distance from the service or separately derived system disconnect - correct-answers-
v v v v v v v v v v v v
Included in the manufactures instructions v v v v
Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ? - correct-
v v v v v v v v v v v v v v v v v
answers-EVJ
Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be remo
v v v v v v v v v v v v v v v v v v
ved - correct-answers-Type S fuse
v v v v
Service drops Installed over roof shall have a vertical clearance of ____ above the roof surface, and u
v v v v v v v v v v v v v v v v v
nless a lesser distance is permitted by and exceptions - correct-answers-8'ft
v v v v v v v v v v
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with
v v v v v v v v v v v v v v v v v v
conductors of Class 1 or electric light or power conductors, unless ____. - correct-answers-
v v v v v v v v v v v v v v
Separated by barrier v v
In the critical care areas of health care centers, each patient bed shall be provided with a minimum o
v v v v v v v v v v v v v v v v v v
f ____ duplex receptacles - correct-answers-3 duplex (6 single)
v v v v v v v v
The equipment system shall supply major electric ____ necessary for patient care and basic hospital
v v v v v v v v v v v v v v v
operation - correct-answers-Equipment v v
CORRECT ANSWERS 2025/2026
Type ____ is multiconductor cable identified for use as underground service entrance cable. -
v v v v v v v v v v v v v
correct-answers-Type USE cable
v v v
Knife switch rated for more than 1200 Amps at 250Volts or less - correct-answers-
v v v v v v v v v v v v v
Can be used only as isolating switch, shall not be opened under load
v v v v v v v v v v v v
Track lighting with outlets in a bathroom is not allowed because ? - correct-answers-
v v v v v v v v v v v v v
Track lighting has receptacle
v v v
Where internal combustion engines are used as the prime motor, an on site fuel supply shall be provi
v v v v v v v v v v v v v v v v v
ded with an on premise fuel supply sufficient for not less than ____ hours full demand operation of t
v v v v v v v v v v v v v v v v v v
he system - correct-answers-6 hours
v v v v
Fixed in place X- v v v
ray equipment properly supplied by a branch circuit rated at not over ____ amperes shall be permitt
v v v v v v v v v v v v v v v v
ed to be supplied through a suitable attachment plug cap and hard service cable cord. - correct-
v v v v v v v v v v v v v v v v
answers-30 Amps v
Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - correct-answers-
v v v v v v v v v v v v v
Both ends v
,GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the ____ty
v v v v v v v v v v v v v v v v v v
pe. - correct-answers-Locking
v v
The maximum voltage drop from service point to the last over-current device in a dwelling unit? -
v v v v v v v v v v v v v v v v
correct-answers-4%
v
Which of the following statements best describe the grounding requirement for central vacuum out
v v v v v v v v v v v v v
let - correct-answers-
v v
Accessible non current carrying metal parts are required to be connected to an equipment groundin
v v v v v v v v v v v v v v
g conductor.
v
In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by at l
v v v v v v v v v v v v v v v v
east two branch circuits, which ____permitted to originate from two separate transfer switches on t
v v v v v v v v v v v v v v
he emergency system - correct-answers-Are permitted
v v v v v
Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges ,day
v v v v v v v v v v v v v v v
rooms, or similar areas - correct-answers-Do not include
v v v v v v v
The patient care area is any portion of the healthcare facility where patients are intended to be ____
v v v v v v v v v v v v v v v v v
or ____. - correct-answers-Examined or treated
v v v v v
Each general care area patient bed location in a healthcare facility must be provided with four ____ o
v v v v v v v v v v v v v v v v v
r ____ duplex receptacles - correct-answers-Single or two
v v v v v v v
A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical, care o
v v v v v v v v v v v v v v v v
n a 24 hour basis of ____ or more patients - correct-answers-Four
v v v v v v v v v v v
Where installed to reduce electrical noise for electronic equipment, electrical continuity of the met
v v v v v v v v v v v v v
al raceways shall not be required and metal raceway can terminate a (an) ____ nonmetallic fitting or
v v v v v v v v v v v v v v v v v
spacer on electronic equipment - correct-answers-Listed fitting
v v v v v v
,Feeder and branch circuit conductors within ____ inches of a Ballast shall have an insulation temper
v v v v v v v v v v v v v v v
ature rating not lower than 90°C (194°F) unless supplying a luminaiere marked as suitable for a differ
v v v v v v v v v v v v v v v v
ent insulation temperature - correct-answers-3 inches
v v v v v
Manufactured wiring systems constructed with type MC cable shall be supported and secured at int
v v v v v v v v v v v v v v
ervals not exceeding ____ ft. - correct-answers-6 ft
v v v v v v v
Where a main bonding jumper or a system bonding jumper is a screw only the screw shall be identifi
v v v v v v v v v v v v v v v v v v
ed with a ____ that shall be visible with the screw installed - correct-answers-Green finish
v v v v v v v v v v v v v v
Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the window, c
v v v v v v v v v v v v v v v v v v
ap, or other prominent part to distinguish them from fuses of higher ampere rating - correct-
v v v v v v v v v v v v v v v
answers-Hexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts (volt-
v v v v v v v v v v v v v v v v
amperes) or the nameplate rating, which ever is larger, for each dryer served ? - correct-answers-
v v v v v v v v v v v v v v v
5000 watts v
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of
v v v v v v v v v v v v v
____ windows that are designed to be opened, doors, porches, stairs fire escape or similar locations.
v v v v v v v v v v v v v v v
- correct-answers-3 ft (36 inches)
v v v v v
——
Cartridge fuses of the renewable type shall be permitted to be used only for replacement in existing
v v v v v v v v v v v v v v v v v v
installation is where there is no evidence of over-fusing or tampering. - correct-answers-Class H
v v v v v v v v v v v v v
Branch circuit conductors within ____inches of the ballast shall have an insulation temperature rati
v v v v v v v v v v v v v
ng not lower it 90°C 194°F - correct-answers-3" inches
v v v v v v v v
, The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - correct-answers-8
v v v v v v v v v v v v v v v v
In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground plug ? -
v v v v v v v v v v v v v v v v v v
correct-answers-Combination range hood/microwave oven
v v v v
Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent devic
v v v v v v v v v v v v v v v v v
e up to the equipment served.if ____ the type 3 SPD connection must be a minimum 30'ft of conduct
v v v v v v v v v v v v v v v v v v
or a distance from the service or separately derived system disconnect - correct-answers-
v v v v v v v v v v v v
Included in the manufactures instructions v v v v
Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ? - correct-
v v v v v v v v v v v v v v v v v
answers-EVJ
Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be remo
v v v v v v v v v v v v v v v v v v
ved - correct-answers-Type S fuse
v v v v
Service drops Installed over roof shall have a vertical clearance of ____ above the roof surface, and u
v v v v v v v v v v v v v v v v v
nless a lesser distance is permitted by and exceptions - correct-answers-8'ft
v v v v v v v v v v
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with
v v v v v v v v v v v v v v v v v v
conductors of Class 1 or electric light or power conductors, unless ____. - correct-answers-
v v v v v v v v v v v v v v
Separated by barrier v v
In the critical care areas of health care centers, each patient bed shall be provided with a minimum o
v v v v v v v v v v v v v v v v v v
f ____ duplex receptacles - correct-answers-3 duplex (6 single)
v v v v v v v v
The equipment system shall supply major electric ____ necessary for patient care and basic hospital
v v v v v v v v v v v v v v v
operation - correct-answers-Equipment v v