The purpose of electrical symbols on plans is ____. - Answers to graphically represent electrical products
and systems
The National Electrical Code is a minimum ____ standard. - Answers Safety
The meaning of approved is ____. - Answers acceptable to the authority having jurisdiction Article 100
Def.
As defined in Article 100, a dwelling unit has the following feature(s): ____. - Answers permanent
provisions for living, sleeping, cooking, and sanitation Article 100 Def.
Devices are equipment whose primary function is to carry current, not ____. - Answers utilize electric
energy Article 100 Def.
The NEC requires that a(n) ____ be installed at each conductor splice connection point. - Answers box or
conduit body NEC 300.15
In order that the connections inside an outlet box remain accessible, the NEC requires that a surface
extension from an outlet box cover be made using ____. - Answers flexible conduit NEC 314.22
Exception
Unused knockouts in boxes, spaces for ____________________ in a panel, meter socket enclosures, and
all other similar equipment must be effectively closed. - Answers circuit breakers NEC 110.12(A) & 408.7
Where noncombustible surface material is used on walls or ceilings, outlet boxes must be mounted so
that they will be set back not more than ____ from the face of the surface material. - Answers 1/4 in.
NEC 314.20
All of the following are included when calculating the usable area of a dwelling to compute the required
lighting load, except for ____. - Answers crawl space NEC 220.12
The 20-ampere appliance circuits required by NEC are permitted to serve no other loads, except for -
Answers clock outlets and receptacles that are installed to plug in the cords of gas-fired ranges, ovens,
or counter-mounted cooking units NEC 210.52(B)(2) Exception 1 and 2
NEC Article 210 provides ____ guidelines for locating receptacle outlets in residences. - Answers
mandatory Article 210
Wall receptacles in a habitable room must be placed so they are no further than ____ feet from any
point along the wall. - Answers 6 ft. NEC 210.52(A)(1)
A continuous load shall not exceed ____ of the rating of the branch circuit - Answers 80%
The smallest wire size for which overcurrent protection is specified in the Code is ____. - Answers 14
AWG NEC 210.24, Table 210.24, and 240.3(D)(3)