NICET Sample Exam questions with correct answers
Secondary power for remote supervising station systems shall be capable of normal operation for ___ hours and then operate the system in alarm for ___ minutes? - Answer 24 / 5 A fire alarm system which serves contiguous or noncontiguous properties under one ownership is considered? - Answer Proprietary system An initiating device which is destroyed as a result of operation is what type? - Answer Nonrestorable The delay from the operation of an initiation device to the automatic activation of a fire safety function shall not exceed? - Answer 10 seconds What documentation shall be delivered upon final acceptance of the system? - Answer Owners manual and installation instructions, Record copy of site specific software, Record drawings What does an asterisk (*) designate in NFPA 72? - Answer Explanatory information follows in Annex A What NFPA standard covers smoke detector requirements for HVAC units? - Answer NFPA 90A Equipment constructed and installed in conformity with NFPA 72 shall be? - Answer Listed