NICET LEVEL 1 questions with correct answers
4 wires - Answer what is the maximum number of 14 AWG RHH conductors which can be installed in 1/2 rigid metal conduit? 3.5'-48" to the actuator - Answer Which of the following would be an appropriate mounting height for a pull station? 1 flash per second - Answer What is the minimum flash rate for a visible notification device? 90" to the top of the device - Answer What is the minimum mounting height for audible notification devices? Such that the entire lens is not less then 80" - Answer What is the minimum mounting height for visible notification devices? Voltage=Current X Resistence - Answer What is the formula for Ohm's Law Put your meter in series with the circuit - Answer When using your mult-meter to measure, you must: Semi-annually - Answer Waterflow devices shall be tested with that frequency? Annually - Answer With what frequency shall ionization smoke detectors be given a functional test? 24 hours in normal operation, 5 minutes in alarm - Answer What are the standby power requirements for a proprietary signaling system?