BANK 2026 UPDATED QUESTIONS AND
ANSWERS GRADED A+
⩥ A cooling load calculation estimates the sensible heat gain of a
structure. The maximum sensible capacity of a cooling-only system
should be within ____% of this calculated value.
a. ±10%
b. +10%
c. +15%
d. +30%. Answer: c (+15%)
⩥ The maximum sensible cooling capacity of a heat pump should be
within ____% of the calculated sensible heat gain of a structure with a
large heating load.
a. ±10%
b. +15%
c. -25%
d. +25%. Answer: d (+25%)
,⩥ The combined output of a heat pump and its auxiliary heat should not
exceed the calculated heat loss of a home by more than ____%.
a. 10%
b. 15%
c. 20%
d. 25%. Answer: b (15%)
⩥ What amount of auxiliary electric heat is needed when the output of a
heat pump on a design day equals 18,800 Btuh and the heat loss of a
home is 29,700 Btuh?
a. 2.1 kWh
b. 3.2 kWh
c. 5.0 kWh
d. 10.9 kWh
Note: 3,413 Btu/kW. Answer: b (3.2 kWh)
⩥ The three processes that transfer heat energy are conduction,
convection, and ____.
a. concentration
,b. radiation
c. refraction
d. static pressure. Answer: b (radiation)
⩥ Heat transfer that occurs when substances of different temperatures
are in contact with each other is called ____.
a. concentration
b. conduction
c. convection
d. radiation. Answer: b (conduction)
⩥ What effect does raising the pressure in a sealed system have on
refrigerant?
a. It becomes more difficult to subcool the liquid refrigerant
b. It becomes more difficult to superheat the refrigerant vapor
c. The refrigerant's boiling point decreases
d. The refrigerant's boiling point increases. Answer: d (The refrigerant's
boiling point increases)
⩥ What is the primary danger to people near an accidental refrigerant
release or spill?
, a. Blurred vision caused by the refrigerant vapor coming in contact with
the eyes
b. Changes in weather patterns caused by global warming
c. Damage to the food chain caused by decreased ozone levels in the
stratosphere
d. Suffocation caused by the heavier refrigerant displacing oxygen in the
air. Answer: d (Suffocation caused by the heavier refrigerant displacing
oxygen in the air)
⩥ The maximum temperature at which refrigerant may be stored is
____°F when the container is no more than ____% full of liquid by
volume.
a. 120°F, 60%
b. 125°F, 60%
c. 125°F, 80%
d. 135°F, 80%. Answer: c (125°F, 80%)
⩥ Boiling of the refrigerant occurs in which system component?
a. Compressor
b. Condenser
c. Evaporator