class II, division 1 locations require interlocked armor type MC cable having an
overall jacket of suitable polymeric material and provided with termination fittings
and - ANSWER ✓ LFLC with listed fittings
class III locations are hazardous because of the presence of _ or where materials
producing combustible flyings are handled, manufactured, or used even though
they are not likely to be airborne in quantities sufficient to produce ignitable
mixtures - ANSWER ✓ easily ignitable fibers
branch circuits are recognised by article 210 shall be rated in accordance with the
maximum permitted ampere rating or setting of the _ - ANSWER ✓ overcurrent
device
individual movable showcases can be connected by - ANSWER ✓ flexible cord to
permanently installed receptacles
in cord-connected showcases, the secondary circuit of each electric-discharge
lighting ballasts is (are) - ANSWER ✓ limited to one showcase
receptacles, connectors, and attachment plugs for showcases must be of a listed
grounding type, rated _ - ANSWER ✓ 15 or 20 amps
receptacles on a branch circuit are calculated at _ per strap - ANSWER ✓ 180
volt-amperes
, a continuous load is defined as a load - ANSWER ✓ having the maximum level of
current sustained for three hours or more
in hotel and motel guest rooms and suites, _ do not require a receptacle -
ANSWER ✓ hallways
wall switch controlled lighting outlets are not required in commercial occupancies,
except for containing equipment that requires servicing - ANSWER ✓ attics and
underfloor spaces
general purpose receptacles are - ANSWER ✓ not continuous loads
sign and outline lighting outlets in commercial wire buildings are computed at a
minimum of _ volt amperes - ANSWER ✓ 1200
a load where the maximum current is expected to continue for _ or more is a
continuous load - ANSWER ✓ 3 hours
feeder conductors and overcurrent protection shall be sized at 100% of
noncontinuous loads plus _ % of continuous loads - ANSWER ✓ 125
to calculate multiple noncoincident loads used simultaneously, the _ loads that
will be used at one time is (are) used in calculating the total feeder/service load -
ANSWER ✓ largest
the demand factor for three pieces of equipment is 90%; for four pieces, _%, for
five pieces, 70% and for more than five pieces , 65% - ANSWER ✓ 80%
in determining the load of the highest rated motor, the greater of wither the
ampere rating from 430.22(E) or the largest continuous duty motor full load
current multiplied by _ shall be used in the summation - ANSWER ✓ 1.25
three-phase voltage is found by multiplying the voltage (single phase) by -
ANSWER ✓ 1.732
fractions of an ampere 0.5 and higher are _, while fractions less than 0.5 are
dropped - ANSWER ✓ rounded up