Fire Alarm Level II Actual Exam Preparation Newest
2026 Complete 100 Questions And Correct Answers
(Verified Answers)|Already Graded A+||Latest Exam!!
While testing a fire alarm system at a correctional facility, it
is determined that the general fire alarm signal requires
human intervention to be initiated. This is permitted using
a _____ feature?
A. Pre signal
B. Positive alarm sequence
C. Manual initiation
D. Alarm verification - Answer-A. Pre Signal
NFPA 72 23.8.1.1.2(3)(a)
Consider a 50′ x 50′ room with a 12′ ceiling. What is the
minimum intensity required for a ceiling mount strobe?
A. 85 cd
B. 110 cd
C. 80 cd
,2|Page
D. 95 cd - Answer-D. 95 cd
NFPA 72 Table 18.5.5.1.1(b)
Consider a smoke control system with a stairwell
pressurization system. A _____ shall be provided in the air
supply to the pressurized stairwell.
A. Supervisory switch to monitor fan operation
B. Manual fire alarm box
C. Heat detector
D. Smoke detector - Answer-D. Smoke Detector
NFPA 92 - 6.4.6.2.1
NFPA 72 states that smoke detector spacing shall be
reduced where the airflow in a defined space exceeds
_____ air changes per hour?
A. 6
B. 7
C. 6.5
D. 7.5 - Answer-D. 7.5
, 3|Page
NFPA 72 17.7.6.3.3.1
Which of the following requires a visual inspection
frequency of quarterly? (Select Two)
A. Waterflow devices
B. Radiant energy detectors
C. Smoke detectors
D. Visible notification appliances - Answer-A. Waterflow
devices
B. Radiant energy detectors
NFPA 72 Table 14.3.1
A project in an unsprinklered facility is using CI (circuit
integrity) cable to provide a 2-hour fire rated resistance for
a circuit. What is the pathway survivability rating?
A. Level 1
B. Level 2
C. Level 3
D. Level 4 - Answer-B. Level 2