When a device is inaccessible due to excessive height,
such as an atrium, what it the maximum interval for
testing? - Answer-18 months
When installing a wall-mounted fire telephone appliance to
the public, what is the acceptable maximum mounting
height from the floor? - Answer-66 inches
Elevator lobby smoke detectors shall be mounted within a
maximum of which distance from the center-line of the
door? - Answer-21 feet
At minimum, when working near power lines with voltage
of 600 volts and lower, an aerial lift operator shall maintain
which distance from the lines? - Answer-10 feet
The use of unprotected EMT shall be permitted under
which conditions? - Answer-when in direct contact with the
earth
,2|Page
According to NFPA 70, what is the maximum unsupported
length of 1/2-inch flexible metallic conduit where flexibility
is required after installation? - Answer-4 1/2 feet
What is the maximum bend (in degrees) permitted in a
conduit run between outlet boxes? - Answer-360 Degrees
If the primary power is disconnected and the fire alarm
system goes into an alarm condition, what is the minimum
acceptable time for secondary power to operate the voice
evacuation systems? - Answer-15 minutes
A riser room temperature switch should activate when the
temperature falls below which level? - Answer-40 degrees
F
According to NFPA 72, what is the maximum sound
pressure level permitted in a space with notification
appliances? - Answer-110 dBA
What is the minimum interval for testing a single-station
smoke detector in multifamily units? - Answer-Annually
, 3|Page
Where should a technician install a detector in relation to
beam that is less than 12 inches deep and less that 8 feet
in center? - Answer-At the bottom of the beam
An existing fire alarm cable in a drop ceiling will be
spliced. which one of the following splice locations will
comply with NFPA 70? - Answer-secured inside a listed
box or enclosure
Which function shall be tested for each newly installed
smoke detector? - Answer-smoke entry?
An 180 foot long corridor is 10 feet wide, with a smooth 10
foot ceiling, interrupted by 4-inch beams spaced every 10
feet. How many heat detectors with a listed 30 foot
spacing are required? - Answer-6 heat detectors
At which height must cables be physically protected when
being installed within an exposed ceiling? - Answer-7 feet