1. How frequently should a tank without a supervised low temperature alarm
be inspected?
A). Daily.
B). Weekly.
C). Every other week.
D). Monthly - ANSWER B) Weekly
2. On hose connection pressure reducing valves, adjustment should be made
to what instructions?
A). Authorities Having Jurisdiction guidelines.
B). Insurance underwriters guidelines.
C). Manufacturers guidelines
D) NFPA 14 - ANSWER C) Manufacturers guidelines
,3. A partial flow test of a master pressure reducing valve maybe done using
which method?
A). Closing the main shut off valves.
B). Main drain test on a quarterly basis.
C). Opening the inspectors test valve annually.
D). Turning the fire pump on and opening the case relief valve - ANSWER B)
Main drain test on a quarterly basis
4. If the hydraulically most remote outlet on a standpipe system is not
accessible where shall the flow test be performed?
A). At a location determined by the Authority Having Jurisdiction
B). At the low point drain.
C). At the most convenient site determined by the owner.
D). At the next low hose outlet - ANSWER A) At a location determined by
the Authority Having Jurisdiction
5. How often shall deluge valves be trip tested ?
A) Annually.
6. B). Every three years.
7. C). Every five years.
8. D). Only after changes to the system - ANSWER A) Annually
9. During a test on a fire pump with an electric driver, which two items would
the inspector use?) (Choose two)
A). Calibrator
B) multi meter.
,C). Refractor.
D) Tachometer - ANSWER B) Multimeter D) Tachometer
10.When the initiating device on a high water temperature limit switch cannot
be tested, which alternative testing can be performed?
A) Check the water temperature on the tank discharge.
B). The circuitry can be tested
C). A manual temperature reading can be taken.
D). Testing should be in accordance to NFPA 72 - ANSWER B) The circuitry
can be tested
11.To test a sample containing propylene glycol , from a two inch anti- freeze
loop in a building with a 4 inch wet pipe system and a 4 inch pressure zone
back flow preventer fed by a non potable water supply, which tool should
be used?
A). Anemometer.
B). Refractometer.
C). Spectrometer.
D). Tachometer - ANSWER B) Refractometer
12.Who should be notified before a test of a water spray system is conducted?
A) All personnel who's operations could be affected by the systems
actuation.
B). Only the alarms supervisory service.
, C). Only the Authority Having Jurisdiction.
D). Only the maintenance department - ANSWER A) All personnel who's
operations could be affected by the systems actuation
13.Which three data elements for the inspection of a pre-action system shall
be recorded and maintained at the system riser? (Choose three).
A). Date of the last trip test.
B) Inspectors name.
C). Internal condition of the valve
D). Tripping time - ANSWER A) Date of last trip test B) Inspectors name C)
Tripping time
14. Low temperature alarms, if installed in valve enclosure, shall be inspected
how frequently at the beginning of the heating season? A). Daily for the first
week of the season. B) weekly. C). Quarterly. D). Annually - ANSWER D)
Annually
15. A planned temporary shut down of a system as part of performing the
routine inspection, testing, and maintenance of that system while under
constant attendance of qualified personnel and where system can be
restored to service-quickly should be considered which type of
deficiency/impairment? A). Emergency impairment. B). Non-Critcal
deficiency. C). Pre planned Impairment. D) This is not an impairment -
ANSWER D) This is not an impairment