If the primary power is disconnected and the fire alarm system
goes into an alarm condition, what is the minimum acceptable
time for secondary power to operate the voice evacuation
systems? - THE CORRECT ANSWER-15 minutes
A riser room temperature switch should activate when the
temperature falls below which level? - THE CORRECT ANSWER-40
degrees F
According to NFPA 72, what is the maximum sound pressure
level permitted in a space with notification appliances? - THE
CORRECT ANSWER-110 dBA
What is the minimum interval for testing a single-station smoke
detector in multifamily units? - THE CORRECT ANSWER-Annually
Where should a technician install a detector in relation to beam
that is less than 12 inches deep and less that 8 feet in center? -
THE CORRECT ANSWER-At the bottom of the beam
, An existing fire alarm cable in a drop ceiling will be spliced.
which one of the following splice locations will comply with
NFPA 70? - THE CORRECT ANSWER-secured inside a listed box or
enclosure
Which function shall be tested for each newly installed smoke
detector? - THE CORRECT ANSWER-smoke entry?
An 180 foot long corridor is 10 feet wide, with a smooth 10 foot
ceiling, interrupted by 4-inch beams spaced every 10 feet. How
many heat detectors with a listed 30 foot spacing are required? -
THE CORRECT ANSWER-6 heat detectors
At which height must cables be physically protected when being
installed within an exposed ceiling? - THE CORRECT ANSWER-7 feet
When shall smoke detectors be installed during the
construction process? - THE CORRECT ANSWER-After the final
cleanup of all trades
Where structural members are provided, intermediate metal
conduit shall be secured within which maximum distance from
an outlet box" - THE CORRECT ANSWER-3 feet
The requirement forbidding fire alarm circuits from being T-
tapped, unless indicated by the manufacturer's instructions, is
intended to prevent which type of improper malfunction? - THE
CORRECT ANSWER-monitoring integrity of installation conductors?