Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
How often shall alarm notification appliances to be tested?
A) every month
B) every 3 months
C) every 6 months
D) every 12 months - (ANSWER)D) every 12 months
What is the height of the manual fire alarm boxes shall be a minimum of and a maximum of Inches,
measure vertically from the floor level to the activation handle or leveler of the box. - (ANSWER)42
inches to 48 inches 2014 B.C 970.4.2.2
What color is the fire alarm boxes shall be In color? - (ANSWER)Red 2014 BC 907.4.2.3
What size is raceways when it installed shall be minimum Trade size. - (ANSWER)3/4" EC 2011 760.24
All supports bolts, straps, fitting or other enclosures a bushing shall be of materials. -
(ANSWER)Corrosión resistant NEC 2008 344.10 (B)(1)(D)
Wall mounted appliances shall be mounted such that the entire lens is not less than inches and not
greater than Inches in AFF. - (ANSWER)80 inches & 96 inches NFPA72 18.5.5.1
Penetrations through rated walls, ceilings and floors shall be - (ANSWER)Fire stopped EC: 760.13 (c)(1)
Covers of the boxes, enclosures and cabinets shall be painted And permanently identified as to use. -
(ANSWER)Red E.C. 760.131 (c)(1)
FLP conductors shall not be smaller than AWG. - (ANSWER)18 Awg NYC E.C. 760.0142
If the combination audible/visible appliances are installed, the location of the installation appliance shall
be determined by the requirement of
,Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
A) audible appliances
B) visible appliances
C) the NEC
D) the AHJ - (ANSWER)Answer is B. NFPA 72 2016 18.4.8
What is the maximum number of 12-gauge THHN conductors that can be installed in 1 inch EmT?
(A) 26
(B) 35
(C) 19
(D) 32 - (ANSWER)(26) NEC 2014 Annec C look Table C.1
Two resisters are connected in parallel. R1 = 300 OHMS, R2 = 300 OHMS. What is their equivalent
resistance?
A) 600
B) 300
C) 150
D) 100 - (ANSWER)R= 300 OHMs /2 =150 ohms
Fire-warning equipment to be installed in residential occupancy shall produce the audible emergency
evacuation signal described in
A) NFPA 101
B) NFPA 72
C) ANSI S3.41
D) OSHA - (ANSWER)C) NFPA 72 index residential occupancies
Under Household fire alarm system
According to NPFA 72, the minimum number of restorable fixed-temperature spot-type heat detectors
that must be tested during each annual test is:
,Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
A) all detectors must be tested
B) one detector on each initiating device circuit
C) two detectors or more on each initiating device circuit
D) 75% of all detectors on that circuit - (ANSWER)C) NFPA 72: index Heat detectors> inspection, testing
14.4.4.5
What's color code requirement for a spot-type heat detector rated at 200 degrees Fahrenheit?
A) white
B) blue
C) red
D) green - (ANSWER)NFPA 72 index Heat detectors > color coding: (A)
Otherwise, recommended by the manufacturer's published instructions, single and multiple-station
smoke alarms installed in one or two-family dwellings shall be replaced every
A) 10 years from the date of installations
B) 10 years from the date of manufacture
C) 5 years from the date of installations
D) 5 years from the date of manufacture - (ANSWER)B) NPFA 72 index: single-station alarm scroll
through to section: 14.4.5.4.1
When testing a water level supervisory Switch serving a pressure tank, a single shall indicate if the water
level. from the required level.
A) rises or falls 3 inches
B) rises over 4 inches
C) rise over 12 inches
D) rise of fall la over 12 inches - (ANSWER)NFPA 72
Index: testing: water level switch: to find answer under Method. (A)
, Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
Fire alarm cable are permitted to be strapped to conduit to support the cable?
A) true
B) false
C) only when the cable is within a dropped ceiling - (ANSWER)NEC: go to index: fire alarm systems>
power limited circuits > conductors support: (B)
Where non power-limited wiring is installed exposed, it must be mechanically protected within_of the
finished floor.
A) 7 feet
B) 8 feet
C) 9 feet
D) none of the above - (ANSWER)(A)
If the system impairment occurs, the owner must be notified_______ within ___________.
A) verbally/24 hours
B) in writing/4 hours
C) verbally/4 hours
D) in writing/24 hours - (ANSWER)D) NFPA 72 go to index: impairments (D)
Conductors returning to the fire alarm control panel from the last field device on the circuit might
indicate a ______ circuit
A) class A
B) class B
C) class I
D) class 3 - (ANSWER)Class A (A)
Secondary power supplies for an emergency voice/alarm communications fire alarm system shall be
capable of operating for minimum of ______ of standby followed by ______ of alarm.
Answers (Verified Answers)|Already Graded A+
How often shall alarm notification appliances to be tested?
A) every month
B) every 3 months
C) every 6 months
D) every 12 months - (ANSWER)D) every 12 months
What is the height of the manual fire alarm boxes shall be a minimum of and a maximum of Inches,
measure vertically from the floor level to the activation handle or leveler of the box. - (ANSWER)42
inches to 48 inches 2014 B.C 970.4.2.2
What color is the fire alarm boxes shall be In color? - (ANSWER)Red 2014 BC 907.4.2.3
What size is raceways when it installed shall be minimum Trade size. - (ANSWER)3/4" EC 2011 760.24
All supports bolts, straps, fitting or other enclosures a bushing shall be of materials. -
(ANSWER)Corrosión resistant NEC 2008 344.10 (B)(1)(D)
Wall mounted appliances shall be mounted such that the entire lens is not less than inches and not
greater than Inches in AFF. - (ANSWER)80 inches & 96 inches NFPA72 18.5.5.1
Penetrations through rated walls, ceilings and floors shall be - (ANSWER)Fire stopped EC: 760.13 (c)(1)
Covers of the boxes, enclosures and cabinets shall be painted And permanently identified as to use. -
(ANSWER)Red E.C. 760.131 (c)(1)
FLP conductors shall not be smaller than AWG. - (ANSWER)18 Awg NYC E.C. 760.0142
If the combination audible/visible appliances are installed, the location of the installation appliance shall
be determined by the requirement of
,Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
A) audible appliances
B) visible appliances
C) the NEC
D) the AHJ - (ANSWER)Answer is B. NFPA 72 2016 18.4.8
What is the maximum number of 12-gauge THHN conductors that can be installed in 1 inch EmT?
(A) 26
(B) 35
(C) 19
(D) 32 - (ANSWER)(26) NEC 2014 Annec C look Table C.1
Two resisters are connected in parallel. R1 = 300 OHMS, R2 = 300 OHMS. What is their equivalent
resistance?
A) 600
B) 300
C) 150
D) 100 - (ANSWER)R= 300 OHMs /2 =150 ohms
Fire-warning equipment to be installed in residential occupancy shall produce the audible emergency
evacuation signal described in
A) NFPA 101
B) NFPA 72
C) ANSI S3.41
D) OSHA - (ANSWER)C) NFPA 72 index residential occupancies
Under Household fire alarm system
According to NPFA 72, the minimum number of restorable fixed-temperature spot-type heat detectors
that must be tested during each annual test is:
,Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
A) all detectors must be tested
B) one detector on each initiating device circuit
C) two detectors or more on each initiating device circuit
D) 75% of all detectors on that circuit - (ANSWER)C) NFPA 72: index Heat detectors> inspection, testing
14.4.4.5
What's color code requirement for a spot-type heat detector rated at 200 degrees Fahrenheit?
A) white
B) blue
C) red
D) green - (ANSWER)NFPA 72 index Heat detectors > color coding: (A)
Otherwise, recommended by the manufacturer's published instructions, single and multiple-station
smoke alarms installed in one or two-family dwellings shall be replaced every
A) 10 years from the date of installations
B) 10 years from the date of manufacture
C) 5 years from the date of installations
D) 5 years from the date of manufacture - (ANSWER)B) NPFA 72 index: single-station alarm scroll
through to section: 14.4.5.4.1
When testing a water level supervisory Switch serving a pressure tank, a single shall indicate if the water
level. from the required level.
A) rises or falls 3 inches
B) rises over 4 inches
C) rise over 12 inches
D) rise of fall la over 12 inches - (ANSWER)NFPA 72
Index: testing: water level switch: to find answer under Method. (A)
, Fire Alarm Level 1 Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct
Answers (Verified Answers)|Already Graded A+
Fire alarm cable are permitted to be strapped to conduit to support the cable?
A) true
B) false
C) only when the cable is within a dropped ceiling - (ANSWER)NEC: go to index: fire alarm systems>
power limited circuits > conductors support: (B)
Where non power-limited wiring is installed exposed, it must be mechanically protected within_of the
finished floor.
A) 7 feet
B) 8 feet
C) 9 feet
D) none of the above - (ANSWER)(A)
If the system impairment occurs, the owner must be notified_______ within ___________.
A) verbally/24 hours
B) in writing/4 hours
C) verbally/4 hours
D) in writing/24 hours - (ANSWER)D) NFPA 72 go to index: impairments (D)
Conductors returning to the fire alarm control panel from the last field device on the circuit might
indicate a ______ circuit
A) class A
B) class B
C) class I
D) class 3 - (ANSWER)Class A (A)
Secondary power supplies for an emergency voice/alarm communications fire alarm system shall be
capable of operating for minimum of ______ of standby followed by ______ of alarm.