QUESTIONS AND CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+
Sprinkler system must NOT be shut off or impaired while hot work is performed - (ANSWER)Place
damp cloth guards on individual sprinkler heads
The person conducting the fire watch ______ have other duties - (ANSWER)CANNOT
A portable fire extinguisher with a rating of _________ is required and should be within ____ feet travel
distance hot work area - (ANSWER)2-A:20-B:C///30
For ROOFING OPERATIONS, a portable fire extinguisher with a minimum rating of ______ is required
- (ANSWER)3-A:40-B:C
Fire watch on floors below is ______ - (ANSWER)required
The fire watch must continue for a minimum of ____ minutes after the hot work is done - (ANSWER)30
For any CNG or LPG torch operations, the first inspection shall be conducted ___ minutes after
completion. The second inspection shall be conducted _______ after completion of torch operations. -
(ANSWER)30 min///1 hour
, FDNY G60 EXAM NEWEST 2025 ACTUAL EXAM COMPLETE 70
QUESTIONS AND CORRECT DETAILED ANSWERS (VERIFIED
ANSWERS) |ALREADY GRADED A+
The fire guard or fire watch personnel must complete a signed inspection report and it must be submitted
to and retained by the person in charge of the torch operations. - (ANSWER)The report must be made
available and maintained on the premises for a minimum of 48 hours after the work is complete.
Most common fuel gasses used in blowtorches are ______ - (ANSWER)LPG (butane, propane) natural
gas (methane) (either CNG or piped natural gasses)
Soldering and brazing temperatures are typically______ - (ANSWER)840 degrees F
Oxy-acetylene generates the highest temperature which can reach up to _____ - (ANSWER)6000 degrees
F
Gas torches can exceed _________ and are used for burning weeds, melting ice, or applying tar to a roof -
(ANSWER)2000 degrees F
If the torch operation is to stop for a period of _________________, the torch vale must be closed and the
gas supply to the torch must be completely shut - (ANSWER)1 hour or more