II Exam 2026 | Complete Questions and
Correct Answers | Verified Answers
Assuming that there are no approved separations between conductors, which of
the following conductors are permitted in the same cable or raceway as power-
limited circuit conductors?
Select one:
a.Class 1
b.Class 2
c.Non-power-limited
d.None of the above ---------CORRECT ANSWER-----------------b.Class 2
Which cable type is permitted to be installed exposed in a plenum space?
Select one:
a.FPLP
b.FPLR
c.NPLFP
d.NPLFR ---------CORRECT ANSWER-----------------a.FPLP
Failure to remove conduit burrs usually results in ? .
Select one:
,a.ground faults
b.higher loop resistance
c.open circuits
d.supervisory signals ---------CORRECT ANSWER-----------------a.ground faults
The proper non-power-limited cable for riser use is ? .
Select one:
a.FPLP
b.FPLR
c.NPLF
d.NPLFR ---------CORRECT ANSWER-----------------d.NPLFR
Under what conditions can abandoned fire alarm cables remain in a building?
Select one:
a.When they are difficult to remove
b.When they are installed above a ceiling
c.When they are installed in accessible areas
d.When they are tagged for future use ---------CORRECT ANSWER-----------------
d.When they are tagged for future use
Non-power-limited circuits may be wired using which of the following?
Select one:
,a.THHN in EMT
b.Type CMP cable
c.Type FPLP cable
d.Type FPLR cable ---------CORRECT ANSWER-----------------a.THHN in EMT
Where non-power-limited wiring is installed exposed, it must be mechanically
protected within ? of the finished floor.
Select one:
a.3'
b.5'
c.7'
d.9' ---------CORRECT ANSWER-----------------c.7'
Fire alarm circuit conductors above a suspended ceiling may use the same
support wires that support the ceiling grid.
Select one:
True
False ---------CORRECT ANSWER-----------------False
Fire alarm cables are permitted to be strapped to other conduit.
Select one:
True
, False ---------CORRECT ANSWER-----------------False
Which article of the NEC covers burglary system wiring?
Select one:
a.Article 725
b.Article 727
c.Article 760
d.None of the above ---------CORRECT ANSWER-----------------a.Article 725
Non-power-limited circuits operate with voltages up to ? .
Select one:
a.150 V
b.300 V
c.600 V
d.750 V ---------CORRECT ANSWER-----------------c.600 V
Tables ? and ? provide limitations for power-limited circuits.
Select one:
a.10A / 10B
b.11A / 11B
c.12A / 12B