100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached 4.6 TrustPilot
logo-home
Exam (elaborations)

Master Electrician 211 Exam Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct Detailed Answers (Verified Answers) |Brand New Version!!

Rating
-
Sold
-
Pages
41
Grade
A+
Uploaded on
30-09-2025
Written in
2025/2026

Master Electrician 211 Exam Actual Exam Preparation Newest 2025/2026 Complete Questions And Correct Detailed Answers (Verified Answers) |Brand New Version!!

Institution
Master Electrician 211 Ex
Course
Master Electrician 211 Ex











Whoops! We can’t load your doc right now. Try again or contact support.

Written for

Institution
Master Electrician 211 Ex
Course
Master Electrician 211 Ex

Document information

Uploaded on
September 30, 2025
Number of pages
41
Written in
2025/2026
Type
Exam (elaborations)
Contains
Questions & answers

Subjects

Content preview

Master Electrician 211 Exam Actual Exam Preparation
Newest 2025/2026 Complete Questions And Correct
Detailed Answers (Verified Answers) |Brand New
Version!!

What is the maximum number of overcurrent devices that
the National Electrical Code permits in one
PANELBOARD for lighting and appliance branch circuits?
- 100 correct answer as-42

article 408.36 (exceptions #2)

The CONTINUITY of the GROUNDED CONDUCTOR of a
branch circuit is NOT permitted to be dependent on
receptacle device connections in ___________ circuits. -
100 correct answer as-Multiwire

article 200.2 (B) ( informational notes)

All of the following types of 120 - volt LIGHTING
FIXTURES are permitted on the ceiling of a clothes closet
EXCEPT a(n): - 100 correct answer as-Incandescent
open lamp

article 410.16 (B)

An ATTACHMENT PLUG is permitted to be used as the
disconnect for a room AIR CONDITIONER where: - 100

,correct answer as-Approved means is provided on
the unit

article 440.13

Electric APPLIANCE nameplates are required to be
visible, or to be _____________ - 100 correct answer
as-Easily accessible

article 422.60 (B)

EQUIPMENT shall be installed and used in accordance
with instructions included: - 100 correct answer as-In
the listing or labeling

article 110.3 (informational notes #2)

Given: The rated load current for an AIR - CONDITIONED
COMPRESSOR is 30 amperes. A 50 ampere breaker will
NOT holding the starting current.

The maximum size breaker permitted for branch circuit
protection is ___________ amps. - 100 correct
answer as-60

article 440.22

Where a FLUORESCENT LUMINARIE is connected to a
multiwire branch circuit, the DISCONNECTING MEANS

,for the luminaire is required to simultaneously break: -
100 correct answer as-The ungrounded and
grounded supply conductors to the ballast

article 410.130 (G) (2)

All 15 - and 20 - ampere, 125 - volt, general - purpose
receptacles in a new dwelling are required to be: - 100
correct answer as-Grounding - type

article 406.4 (A)

FIXED OUTDOOR ELECTIC DEICING and snow - melting
equipment shall be considered as a ____________ load. -
100 correct answer as-Continuous

article 426.4

The disconnect for heating and air conditioning shall be
installed a maximum of ___________ feet from the
equipment. - 100 correct answer as-50

article 100 (within sight)

Given: A motor - control circuit is tapped from the load
side of the motor short - circuit protective device. The
control circuit conductor are 14 AWG THWN copper . The
conductors require only short - circuit protection and do

, not extend beyond the motor - control equipment
enclosure.

The maximum overcurrent protection permitted for this
motor - control conduit is ____________ amperes. - 100
correct answer as-100

table 430.72 (B)

Given: The CONTROLLER is not a molded case switch or
a inverse - time circuit.

The motor controlled for a 120 - hp motor must be RATED
at not less than _____________ hp. - 100 correct
answer as-120

430.83 (A) (1)

Given: An inverse - time circuit breaker is used to protect a
hermetic motor - compressor from overload.

The inverse - time circuit breaker shall be rated at a
maximum of __________ percent of rated load current. -
100 correct answer as-115

article 440.12 (A) (1)

Disregarding any exceptions, the MAXIMUM PERMITTED
OPERATIONAL SETTING OF AN ADJUSTABLE
$26.99
Get access to the full document:

100% satisfaction guarantee
Immediately available after payment
Both online and in PDF
No strings attached

Get to know the seller
Seller avatar
studycase

Get to know the seller

Seller avatar
studycase Chamberlain College Nursing
View profile
Follow You need to be logged in order to follow users or courses
Sold
0
Member since
8 months
Number of followers
0
Documents
86
Last sold
-

0.0

0 reviews

5
0
4
0
3
0
2
0
1
0

Recently viewed by you

Why students choose Stuvia

Created by fellow students, verified by reviews

Quality you can trust: written by students who passed their tests and reviewed by others who've used these notes.

Didn't get what you expected? Choose another document

No worries! You can instantly pick a different document that better fits what you're looking for.

Pay as you like, start learning right away

No subscription, no commitments. Pay the way you're used to via credit card and download your PDF document instantly.

Student with book image

“Bought, downloaded, and aced it. It really can be that simple.”

Alisha Student

Frequently asked questions