Master Electrician 211 Exam Actual Exam Preparation
Newest 2025/2026 Complete Questions And Correct Detailed
Answers (Verified Answers) |Brand New Version!!
Conductors that supply a RESISTANCE WELDER shall be protected by
an overcurrent device rated or set at a maximum of _____________
percent of the conductor rating. - SOLUTION=300
article 630.32 (B)
Given: In a mobile - home park, the computed load for each mobile
home is 15,000 VA and the park will have 25 mobile homes. the service
will be a single main, 120/240 - volt service.
The electrical service required for this mobile - home park shall be at
least __________ amps. - SOLUTION=1600
The metal frame of a CIRCULATING POOL PUMP that is
PERMANENTLY wired and located outside is required to : -
SOLUTION=Have GFCI protection
article 680.22 (A) (2)
,2|Page
Bare, green insulation or green with yellow stripes insulation is
generally used for which type of conductors? - SOLUTION=Equipment
grounding conductor
article 250.119
The maximum total rating of FASTENED IN PLACE utilization
equipment permitted on a 20 - ampere branch circuit that also serves
lighting is ___________ amps. - SOLUTION=20
article 210.23 (A) (2)
On a 20 - ampere small - appliance circuit with three outlets, what rating
of receptacles is permitted? - SOLUTION=20 amperes only
table 210.21 (B) (3)
ARE CLASS 2 REMOTE - CONTROL cables permitted to be
STRAPPED or otherwise attached to RACEWAYS for support ?
A) No, this is prohibited
B) Yes, if the raceway is supported properly according to the NEC
,3|Page
C) Yes, if the raceway is not flexible but rigid, such as rigid metal
conduit, electrical metallic tubing, etc.
D) Yes, if the raceway contains power supply conductors for equipment
which the class 2 circuit conductors control - ANSWER-No, this is
prohibited
article 725.143
Where flexible cord is connected to the building ceiling with a suitable "
tension take - up device" the maximum length of the cord from the
supply joint to the take - up device is _____________ feet.
A) 2
B) 4
C) 6
D) 8 - ANSWER-6
article 368.56 (B) (2)
All of the following WIRING METHODS are permitted in a ceiling
space used as a return - air plenum except:
A) IMC
, 4|Page
B) NMC
C) EMT
D) MI CABLE - ANSWER-NMC
article 300.22 (B)
Excluding exceptions, nonmetallic sheathed cable is permitted in all of
the following areas EXECPT: - ANSWER-Above a suspended ceiling of
a retail store
article 334.12 (A) (2)
The NEC permits 3/8 - inch FLEXIBLE METAL CONDUIT to be
unsupported for tap connection to light fixtures, provided the length
doses not exceed __________ feet. - ANSWER-6
article 348.20 (2) (C)
What is the maximum spacing between supports, in ft., for 3/4 - inch,
rigid nonmetallic conduit? - ANSWER-3
table 352.30