How often shall alarm notification appliances to be tested?
A) every month
B) every 3 months
C) every 6 months
D) every 12 months - Answer-D) every 12 months
What is the height of the manual fire alarm boxes shall be
a minimum of and a maximum of Inches, measure
vertically from the floor level to the activation handle or
leveler of the box. - Answer-42 inches to 48 inches 2014
B.C 970.4.2.2
What color is the fire alarm boxes shall be In color? -
Answer-Red 2014 BC 907.4.2.3
,2|Page
What size is raceways when it installed shall be minimum
Trade size. - Answer-3/4" EC 2011 760.24
All supports bolts, straps, fitting or other enclosures a
bushing shall be of materials. - Answer-Corrosión resistant
NEC 2008 344.10 (B)(1)(D)
Wall mounted appliances shall be mounted such that the
entire lens is not less than inches and not greater than
Inches in AFF. - Answer-80 inches & 96 inches NFPA72
18.5.5.1
Penetrations through rated walls, ceilings and floors shall
be - Answer-Fire stopped EC: 760.13 (c)(1)
Covers of the boxes, enclosures and cabinets shall be
painted And permanently identified as to use. - Answer-
Red E.C. 760.131 (c)(1)
FLP conductors shall not be smaller than AWG. - Answer-
18 Awg NYC E.C. 760.0142
,3|Page
If the combination audible/visible appliances are installed,
the location of the installation appliance shall be
determined by the requirement of
A) audible appliances
B) visible appliances
C) the NEC
D) the AHJ - Answer-Answer is B. NFPA 72 2016 18.4.8
What is the maximum number of 12-gauge THHN
conductors that can be installed in 1 inch EmT?
(A) 26
(B) 35
(C) 19
(D) 32 - Answer-(26) NEC 2014 Annec C look Table C.1
Two resisters are connected in parallel. R1 = 300 OHMS,
R2 = 300 OHMS. What is their equivalent resistance?
A) 600
, 4|Page
B) 300
C) 150
D) 100 - Answer-R= 300 OHMs /2 =150 ohms
Fire-warning equipment to be installed in residential
occupancy shall produce the audible emergency
evacuation signal described in
A) NFPA 101
B) NFPA 72
C) ANSI S3.41
D) OSHA - Answer-C) NFPA 72 index residential
occupancies
Under Household fire alarm system
According to NPFA 72, the minimum number of restorable
fixed-temperature spot-type heat detectors that must be
tested during each annual test is:
A) all detectors must be tested
B) one detector on each initiating device circuit
C) two detectors or more on each initiating device circuit
D) 75% of all detectors on that circuit - Answer-C) NFPA
72: index Heat detectors> inspection, testing 14.4.4.5