Fire alarm shop drawings are not required including which one of
the following:
A) Name of the protected premises owner and occupant
B) date of issue and any revision dates
C) name of the designer
D) name of the installer or contractor - ANSWER-C) name of the
designer
In commercial construction which of the following phase in listed
out of sequence assuming the sequence is A, B, C, D.
A) Civil preparation
B) Device Trim Out
C) Rough Electrical Installation
D) Testing and commissioning - ANSWER-B) Trim-out
Device Trim out should follow electrical rough in
, Page |2
Which of the following is the owners representative from a
construction project?
A) General contractor
B) Subcontractor
C) Authority having jurisdiction
D) Architect - ANSWER-D) Architect
That architect is hired by the building owner to coordinate the
design, building and acceptance of the building and to represent
the owner rights and interest.
The ________________is responsible for providing any PPE that
is generally required by OSHA such as hardhats, gloves
___________ and is required to supply speciality to PPE such as
respirators.
A) Employees, Employer
B) Employees, Employees
C) Employer, Employer
D) Employer, employee - ANSWER-C) Employer, Employer
, Page |3
The minimum recommended separation for class A primary and
redundant or outgoing conductors installed it vertically and routed
separately to ensure protection of the cables from physical
damage is______________
A) 6 inches
B) 12 inches
C) 36 inches
D) 48 inches - ANSWER-B) 12 inches
Annex A 12.3.8
A circuit powered to wire smoke detector is installed in a class A
initiating device circuit. How many termination will be required at
the fire alarm control unit for this circuit?
A) 2
B) 4
C) 6
D) 8 - ANSWER-B) 4
Annex F
Figured F.2.4
, Page |4
There will be two outgoing conductors and two return conductors.
The activation of the initiating device shall occurs
________________ within seconds of water-flow.
A) 200
B) 10
C) 60
D) 90 - ANSWER-D)
Detectors should not be placed closer than ____________ inches
from a air supply diffuser or return air opening.
A) 12 inches
B) 24 inches
C) 36 inches
D) 48 inches - ANSWER-C) 36 inches
Annex A
17.7.4.1