LOAD CALCULATIONS AND BRANCH
FEEDER CIRCUITS EXAM WITH CORRECT
ACTUAL QUESTIONS AND CORRECTLY
WELL DEFINED ANSWERS LATEST
ALREADY GRADED A+ 2025 – 2026
What is the voltage drop for a 120V, single-phase, two-wire branch
circuit, 100' long, using copper conductors of 6,530 circular mils
with a noncontinuous load of 13A? 5.14V - ANSWERS-5.14V
What size copper conductor would be required for a 240V, 1Ø
circuit supplying a noncontinuous load of 27.5A at a distance of
145', and a maximum voltage drop of 3%? - ANSWERS-No. 10
When connected to 15A or 20A multi-outlet general-purpose
branch circuits, which of the following shall not exceed 50% of the
branch circuit ampere rating? - ANSWERS-Fastened-in-place
utilization equipment