1. One of the significant causes of leaks in underground liquid storage
systems is ____________ ________________ - 🧠 ANSWER ✔✔Improper
Installation
2. Written Plans are required to - 🧠 ANSWER ✔✔obtain permits, solicit
bids, and provide precise guidance for installers.
3. The plans should - 🧠 ANSWER ✔✔Describe the property, identify the
size and location of the tanks, indicate the liquids to be stored and provide
the location of the dispensers and piping.
4. Storage systems discussed in this recommended practice are usually
regulated by - 🧠 ANSWER ✔✔Federal, state or local agencies.
,5. All owners should ensure that the equipment to be installed meets - 🧠
ANSWER ✔✔applicable regulatory requirements before being installed
6. Consult the local authorities who have jurisdiction in the area before
storage-system plans are - 🧠 ANSWER ✔✔finalized or construction is
initiated.
7. All owners should ensure that the equipment to be installed meets all
applicable regulatory requirements before - 🧠 ANSWER ✔✔Being installed.
8. To avoid damage tanks must not be - 🧠 ANSWER ✔✔dropped, dragged,
or handled with sharp objects.
9. Tanks must not be dropped, dragged, or handled with sharp objects to
avoid - 🧠 ANSWER ✔✔Damage to the tank
10. The only time tanks really should be moved is when - 🧠 ANSWER
✔✔for inspections and testing.
11. If a tanks is damaged at all throughout the moving process it must be -
🧠 ANSWER ✔✔Repaired in accordance with the manufacture's
instructions.
,12. The proper way to move a tank is by lifting it, using the - 🧠 ANSWER
✔✔Lift lugs that are installed by the manufacturer.
13. Tanks should be carefully lifted and lowered using - 🧠 ANSWER
✔✔Cables or chains of adequate length.
14. When two lifting lugs are being used, the angle between the lifting cable
and vertical should be no more than - 🧠 ANSWER ✔✔30 degrees.
15. Stockpile piping materials and equipment in a _____________
_________ on the job site - 🧠 ANSWER ✔✔Secure area
16. Confirm adherence to specifications by reporting to the owner about
any - 🧠 ANSWER ✔✔detected damage that could result in leakage or
premature corrosion.
17. Pressure test single-walled tanks with _____ to _______ psig air
pressure, soaping all surfaces, seams and fittings while inspecting for
bubbles. - 🧠 ANSWER ✔✔3 to 5
18. Air testing with over ___ psig (3 Psig for 12-Ft. Diameter FRP tanks) is
hazardous and may damage the tank - 🧠 ANSWER ✔✔5 psig
COPYRIGHT©NINJANERD 2025/2026. YEAR PUBLISHED 2025. COMPANY REGISTRATION NUMBER: 619652435. TERMS OF USE.
PRIVACY STATEMENT. ALL RIGHTS RESERVED
3
, 19. Do not air test a tank that has previously contained - 🧠 ANSWER
✔✔flammable or combustible liquids
20. Place ______ barricades at the ends of tanks being tested. - 🧠
ANSWER ✔✔Warning
21. Avoid tank ends, man-ways, and fittings while the tank is under - 🧠
ANSWER ✔✔Pressure
22. Release pressure in the tank before disconnecting any - 🧠 ANSWER
✔✔gauges or test fittings.
23. Be aware some manufactures do not tighten fittings to allow for
_____________ _____________ during shipping and storage. - 🧠
ANSWER ✔✔Temperature changes
24. True or False: Air tests are inconclusive without soaping and careful
inspection for bubbles? - 🧠 ANSWER ✔✔True
25. Tanks gauges must have a scale that will permit detection of small
changes in __________ that might go undetected on gauges with a
___________ _________. - 🧠 ANSWER ✔✔Pressure, broader range.