1. According to the NEC®, the ampacity of branch circuit conductors
must be derated when there are more than how many current-
carrying conductors in a raceway? - ANSWER ✔ 3
2. What is the current-carrying capacity for No. 6 THWN aluminum
conductors in conduit run through an ambient temperature of
38°C? - ANSWER ✔ 44 Amps
3. What is the lighting load on a 120V circuit for six 100W
incandescent lights and four fluorescent fixtures with a ballast
rating of 1.5A, all operating continuously for 8 hours per day?
13.75A - ANSWER ✔ 13.75A
, 4. What is the load center distance for a 208V, four-wire, three-phase
branch circuit with fixed noncontinuous loads from the source of
60A at 45', 40A at 60', 30A at 75', and 25A at 100' - ANSWER ✔
63.55'
5. What is the load center length for a branch circuit consisting of
noncontinuous loads of 125A at 80', 75A at 110', and 50A at 100'? -
ANSWER ✔ 93'
6. Air conditioning overcurrent protective devices can never exceed
what percentage of the motor-rated load current or the branch
circuit selection current (whichever is greater)? - ANSWER ✔
225%
7. Conductors must be derated when installed in conduit - ANSWER
✔ on or above rooftops
8. Continuous loads are calculated at what percentage of the
maximum current rating of the overcurrent device? - ANSWER ✔
80%
9. For a given load and length, the branch circuit voltage drop should
not exceed - ANSWER ✔ 3%