When the pump is in operation a small water leak on the pump bearings is
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
desirable and should not be considered a malfunction. Additionally, water
|! |! |! |! |! |! |! |! |! |!
should discharge from a ---- relief valve (electric pump) or --- exchanger
|! |! |! |! |! |! |! |! |! |! |! |!
(diesel pump) while the fire pump is operating under a "no-flow" condition. -
|! |! |! |! |! |! |! |! |! |! |! |! |!
Correct answer ✔circulation /heat |! |! |!
A sprinkler system is a - Correct answer ✔fire extinguishing system, other
|! |! |! |! |! |! |! |! |! |! |! |!
than a water mist system, that utilizes water as the extinguishing agent.
|! |! |! |! |! |! |! |! |! |! |!
Inspection, testing, servicing and other maintenance of sprinkler systems
|! |! |! |! |! |! |! |! |!
must be - Correct answer ✔personally supervised and be performed in
|! |! |! |! |! |! |! |! |! |! |!
accordance with NFPA (National Fire Protection Association) #25 2011
|! |! |! |! |! |! |! |! |!
edition.
All multiple dwellings, factories, office buildings, warehouses, stores and
|! |! |! |! |! |! |! |! |!
offices, theaters and music halls, hospitals and asylums, and all public
|! |! |! |! |! |! |! |! |! |! |!
schools and other public buildings, churches and other places where large
|! |! |! |! |! |! |! |! |! |! |!
numbers of persons are congregated for purposes of worship, instruction,
|! |! |! |! |! |! |! |! |! |!
amusement, and all piers, bulkheads, wharves, pier sheds, bulkhead sheds or
|! |! |! |! |! |! |! |! |! |! |!
other waterfront structures shall provide - Correct answer ✔fire
|! |! |! |! |! |! |! |! |!
,extinguishers, buckets, axes, fire hooks, fire doors and other means of |! |! |! |! |! |! |! |! |! |! |!
preventing and extinguishing fires as the commissioner may direct.
|! |! |! |! |! |! |! |!
Required fire protection systems shall be extended or altered as necessary to
|! |! |! |! |! |! |! |! |! |! |! |!
maintain and continued protection whenever - Correct answer ✔the building
|! |! |! |! |! |! |! |! |! |!
or structure is altered. Systems not complying with this section shall be
|! |! |! |! |! |! |! |! |! |! |! |!
considered to be impaired. |! |! |!
It shall be unlawful to install or maintain any fire protection system or device
|! |! |! |! |! |! |! |! |! |! |! |! |!
that has - Correct answer ✔the physical appearance of fire protection
|! |! |! |! |! |! |! |! |! |! |! |!
equipment but that does not perform a fire protection function where it may
|! |! |! |! |! |! |! |! |! |! |! |! |!
be confused with actual fire protection equipment. An example would be a
|! |! |! |! |! |! |! |! |! |! |! |!
CCTV camera that is installed inside a shell that resembles a sprinkler head
|! |! |! |! |! |! |! |! |! |! |! |!
Automatic and non-automatic sprinkler systems shall be inspected, tested and
|! |! |! |! |! |! |! |! |!
maintained as required by NFPA #25 2011 edition by - Correct answer
|! |! |! |! |! |! |! |! |! |! |! |! |!
✔competent person holding a S-12 Certificate of Fitness and employed or |! |! |! |! |! |! |! |! |! |! |!
contracted by the owner, to see that all parts of the system are in good
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
working order, and that the Fire Department connection(s), if any, are ready
|! |! |! |! |! |! |! |! |! |! |! |!
for immediate use by the Fire Department.
|! |! |! |! |! |!
A detailed record shall be kept on the premises or other approved location,
|! |! |! |! |! |! |! |! |! |! |! |! |!
for a minimum of - Correct answer ✔3 years for examination by any
|! |! |! |! |! |! |! |! |! |! |! |! |!
representative of the Fire Department. |! |! |! |!
A supply of at least----extra sprinkler heads shall be kept available on the
|! |! |! |! |! |! |! |! |! |! |! |! |!
premises, to replace promptly any fused or damaged sprinklers. - Correct
|! |! |! |! |! |! |! |! |! |! |!
answer ✔6 |!
,Any head which has ----or has been----1. shall be replaced immediately with
|! |! |! |! |! |! |! |! |! |! |! |!
sprinkler head of similar characteristics such as operating temperature, orifice
|! |! |! |! |! |! |! |! |!
size, deflector orientation and thermal sensitivity. - Correct answer
|! |! |! |! |! |! |! |! |! |!
✔opened/damaged
At least once every ---- years - Correct answer ✔Fire Department connection
|! |! |! |! |! |! |! |! |! |! |! |!
or connections for a sprinkler system shall be subjected to a hydrostatic
|! |! |! |! |! |! |! |! |! |! |! |!
pressure test to demonstrate its suitability for Fire Department use.
|! |! |! |! |! |! |! |! |!
At least once every five years, the Fire Department connection or connections
|! |! |! |! |! |! |! |! |! |! |!
for a sprinkler system shall be subjected to a hydrostatic pressure test to
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
demonstrate its suitability for Fire Department use. The test shall be arranged
|! |! |! |! |! |! |! |! |! |! |!
to be conducted by a ----by a----The contractor shall be hired by----- - Correct
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
answer ✔Master Fire Suppression Piping Contractor/1. a Fire Department
|! |! |! |! |! |! |! |! |!
representative/the owner or the owner's representative. |! |! |! |! |!
There shall be---more employees or individuals contracted by the owner with
|! |! |! |! |! |! |! |! |! |! |!
a----Certificate of Fitness 1. inspect the sprinkler system following the |! |! |! |! |! |! |! |! |! |!
standard of the NFPA 25 of 2011. - Correct answer ✔one/COF
|! |! |! |! |! |! |! |! |! |!
It shall be the -----'s responsibility to maintain the sprinkler system and to
|! |! |! |! |! |! |! |! |! |! |! |! |!
determine the individual qualifications and competencies of the COF holder
|! |! |! |! |! |! |! |! |! |!
that performs the functions related to inspection, testing and maintenance of
|! |! |! |! |! |! |! |! |! |! |!
such system. - Correct answer ✔owner's
|! |! |! |! |!
, The building owner shall assign an ----to comply with the requirements of
|! |! |! |! |! |! |! |! |! |! |! |!
study material. - Correct answer ✔impairment coordinator
|! |! |! |! |! |!
The impairment coordinator shall take the action(s) when - Correct answer
|! |! |! |! |! |! |! |! |! |! |!
✔a standpipe system, sprinkler system or fire alarm system is out of service.
|! |! |! |! |! |! |! |! |! |! |! |!
The impairment coordinator shall maintain records of all - Correct answer
|! |! |! |! |! |! |! |! |! |! |!
✔system inspections, tests, servicing and other items of maintenance
|! |! |! |! |! |! |! |!
The impairment coordinator's records of system inspections, tests, servicing
|! |! |! |! |! |! |! |! |!
and other items of maintenance shall be kept on the premises or other
|! |! |! |! |! |! |! |! |! |! |! |! |!
approved location for a minimum of --- and made available for inspection by
|! |! |! |! |! |! |! |! |! |! |! |! |!
any member of---- - Correct answer ✔3 years/FDNY
|! |! |! |! |! |! |!
In absence of a specific designee,the ---shall be considered the impairment
|! |! |! |! |! |! |! |! |! |! |!
coordinator. - Correct answer ✔building owner |! |! |! |! |!
Planned removal from service: When the system, or a portion of the sprinkler
|! |! |! |! |! |! |! |! |! |! |! |!
system, is placed out of service for a scheduled inspection, testing, regular
|! |! |! |! |! |! |! |! |! |! |! |! |!
maintenance, minor repairs or for construction affecting not more than 1 |! |! |! |! |! |! |! |! |! |! |!
floor, the ---- and ----of and authorize the placing of the system out of service.
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
- Correct answer ✔COF holder/impairment coordinator
|! |! |! |! |!
Unplanned out of service condition - Correct answer ✔A serious defect in the
|! |! |! |! |! |! |! |! |! |! |! |!
sprinkler system including, but not limited to: an empty tank, a break or
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
major leak in the system's water piping, inoperative or shut water supply
|! |! |! |! |! |! |! |! |! |! |! |!
valves, defective fire department connections, construction related shut
|! |! |! |! |! |! |! |!
Exam w ith accu r ate detailed |! |! |! |!
answ er s
When the pump is in operation a small water leak on the pump bearings is
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
desirable and should not be considered a malfunction. Additionally, water
|! |! |! |! |! |! |! |! |! |!
should discharge from a ---- relief valve (electric pump) or --- exchanger
|! |! |! |! |! |! |! |! |! |! |! |!
(diesel pump) while the fire pump is operating under a "no-flow" condition. -
|! |! |! |! |! |! |! |! |! |! |! |! |!
Correct answer ✔circulation /heat |! |! |!
A sprinkler system is a - Correct answer ✔fire extinguishing system, other
|! |! |! |! |! |! |! |! |! |! |! |!
than a water mist system, that utilizes water as the extinguishing agent.
|! |! |! |! |! |! |! |! |! |! |!
Inspection, testing, servicing and other maintenance of sprinkler systems
|! |! |! |! |! |! |! |! |!
must be - Correct answer ✔personally supervised and be performed in
|! |! |! |! |! |! |! |! |! |! |!
accordance with NFPA (National Fire Protection Association) #25 2011
|! |! |! |! |! |! |! |! |!
edition.
All multiple dwellings, factories, office buildings, warehouses, stores and
|! |! |! |! |! |! |! |! |!
offices, theaters and music halls, hospitals and asylums, and all public
|! |! |! |! |! |! |! |! |! |! |!
schools and other public buildings, churches and other places where large
|! |! |! |! |! |! |! |! |! |! |!
numbers of persons are congregated for purposes of worship, instruction,
|! |! |! |! |! |! |! |! |! |!
amusement, and all piers, bulkheads, wharves, pier sheds, bulkhead sheds or
|! |! |! |! |! |! |! |! |! |! |!
other waterfront structures shall provide - Correct answer ✔fire
|! |! |! |! |! |! |! |! |!
,extinguishers, buckets, axes, fire hooks, fire doors and other means of |! |! |! |! |! |! |! |! |! |! |!
preventing and extinguishing fires as the commissioner may direct.
|! |! |! |! |! |! |! |!
Required fire protection systems shall be extended or altered as necessary to
|! |! |! |! |! |! |! |! |! |! |! |!
maintain and continued protection whenever - Correct answer ✔the building
|! |! |! |! |! |! |! |! |! |!
or structure is altered. Systems not complying with this section shall be
|! |! |! |! |! |! |! |! |! |! |! |!
considered to be impaired. |! |! |!
It shall be unlawful to install or maintain any fire protection system or device
|! |! |! |! |! |! |! |! |! |! |! |! |!
that has - Correct answer ✔the physical appearance of fire protection
|! |! |! |! |! |! |! |! |! |! |! |!
equipment but that does not perform a fire protection function where it may
|! |! |! |! |! |! |! |! |! |! |! |! |!
be confused with actual fire protection equipment. An example would be a
|! |! |! |! |! |! |! |! |! |! |! |!
CCTV camera that is installed inside a shell that resembles a sprinkler head
|! |! |! |! |! |! |! |! |! |! |! |!
Automatic and non-automatic sprinkler systems shall be inspected, tested and
|! |! |! |! |! |! |! |! |!
maintained as required by NFPA #25 2011 edition by - Correct answer
|! |! |! |! |! |! |! |! |! |! |! |! |!
✔competent person holding a S-12 Certificate of Fitness and employed or |! |! |! |! |! |! |! |! |! |! |!
contracted by the owner, to see that all parts of the system are in good
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
working order, and that the Fire Department connection(s), if any, are ready
|! |! |! |! |! |! |! |! |! |! |! |!
for immediate use by the Fire Department.
|! |! |! |! |! |!
A detailed record shall be kept on the premises or other approved location,
|! |! |! |! |! |! |! |! |! |! |! |! |!
for a minimum of - Correct answer ✔3 years for examination by any
|! |! |! |! |! |! |! |! |! |! |! |! |!
representative of the Fire Department. |! |! |! |!
A supply of at least----extra sprinkler heads shall be kept available on the
|! |! |! |! |! |! |! |! |! |! |! |! |!
premises, to replace promptly any fused or damaged sprinklers. - Correct
|! |! |! |! |! |! |! |! |! |! |!
answer ✔6 |!
,Any head which has ----or has been----1. shall be replaced immediately with
|! |! |! |! |! |! |! |! |! |! |! |!
sprinkler head of similar characteristics such as operating temperature, orifice
|! |! |! |! |! |! |! |! |!
size, deflector orientation and thermal sensitivity. - Correct answer
|! |! |! |! |! |! |! |! |! |!
✔opened/damaged
At least once every ---- years - Correct answer ✔Fire Department connection
|! |! |! |! |! |! |! |! |! |! |! |!
or connections for a sprinkler system shall be subjected to a hydrostatic
|! |! |! |! |! |! |! |! |! |! |! |!
pressure test to demonstrate its suitability for Fire Department use.
|! |! |! |! |! |! |! |! |!
At least once every five years, the Fire Department connection or connections
|! |! |! |! |! |! |! |! |! |! |!
for a sprinkler system shall be subjected to a hydrostatic pressure test to
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
demonstrate its suitability for Fire Department use. The test shall be arranged
|! |! |! |! |! |! |! |! |! |! |!
to be conducted by a ----by a----The contractor shall be hired by----- - Correct
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
answer ✔Master Fire Suppression Piping Contractor/1. a Fire Department
|! |! |! |! |! |! |! |! |!
representative/the owner or the owner's representative. |! |! |! |! |!
There shall be---more employees or individuals contracted by the owner with
|! |! |! |! |! |! |! |! |! |! |!
a----Certificate of Fitness 1. inspect the sprinkler system following the |! |! |! |! |! |! |! |! |! |!
standard of the NFPA 25 of 2011. - Correct answer ✔one/COF
|! |! |! |! |! |! |! |! |! |!
It shall be the -----'s responsibility to maintain the sprinkler system and to
|! |! |! |! |! |! |! |! |! |! |! |! |!
determine the individual qualifications and competencies of the COF holder
|! |! |! |! |! |! |! |! |! |!
that performs the functions related to inspection, testing and maintenance of
|! |! |! |! |! |! |! |! |! |! |!
such system. - Correct answer ✔owner's
|! |! |! |! |!
, The building owner shall assign an ----to comply with the requirements of
|! |! |! |! |! |! |! |! |! |! |! |!
study material. - Correct answer ✔impairment coordinator
|! |! |! |! |! |!
The impairment coordinator shall take the action(s) when - Correct answer
|! |! |! |! |! |! |! |! |! |! |!
✔a standpipe system, sprinkler system or fire alarm system is out of service.
|! |! |! |! |! |! |! |! |! |! |! |!
The impairment coordinator shall maintain records of all - Correct answer
|! |! |! |! |! |! |! |! |! |! |!
✔system inspections, tests, servicing and other items of maintenance
|! |! |! |! |! |! |! |!
The impairment coordinator's records of system inspections, tests, servicing
|! |! |! |! |! |! |! |! |!
and other items of maintenance shall be kept on the premises or other
|! |! |! |! |! |! |! |! |! |! |! |! |!
approved location for a minimum of --- and made available for inspection by
|! |! |! |! |! |! |! |! |! |! |! |! |!
any member of---- - Correct answer ✔3 years/FDNY
|! |! |! |! |! |! |!
In absence of a specific designee,the ---shall be considered the impairment
|! |! |! |! |! |! |! |! |! |! |!
coordinator. - Correct answer ✔building owner |! |! |! |! |!
Planned removal from service: When the system, or a portion of the sprinkler
|! |! |! |! |! |! |! |! |! |! |! |!
system, is placed out of service for a scheduled inspection, testing, regular
|! |! |! |! |! |! |! |! |! |! |! |! |!
maintenance, minor repairs or for construction affecting not more than 1 |! |! |! |! |! |! |! |! |! |! |!
floor, the ---- and ----of and authorize the placing of the system out of service.
|! |! |! |! |! |! |! |! |! |! |! |! |! |! |!
- Correct answer ✔COF holder/impairment coordinator
|! |! |! |! |!
Unplanned out of service condition - Correct answer ✔A serious defect in the
|! |! |! |! |! |! |! |! |! |! |! |!
sprinkler system including, but not limited to: an empty tank, a break or
|! |! |! |! |! |! |! |! |! |! |! |! |! |!
major leak in the system's water piping, inoperative or shut water supply
|! |! |! |! |! |! |! |! |! |! |! |!
valves, defective fire department connections, construction related shut
|! |! |! |! |! |! |! |!