,Use the collected service data below to calculate the air flow volume for a
residential electric furnace:
Voltage = 240 V ac
Current draw = 40 A
Entering air temperature = 70°F
Leaving air temperature = 105°F
a. 798 cfm
b. 867 cfm
c, 936 cfm
d. 1,100 cfm
cfm = (voltage x current x 3.413) / (temperature rise x 1.08) - Correct Solution b
(867 cfm)
What is the maximum recommended face velocity for air leaving a supply register?
,a. 300 ft/min
b. 450 ft/min
c. 500 ft/min
d. 700 ft/min - Correct Solution d (700 ft/min)
Temperature readings taken on the refrigerant discharge line 6 in. from the
compressor must never exceed ____°F.
a. 150°F
b. 175°F
c. 200°F
d. 225°F - Correct Solution d (225°F)
What problem results when the limit temperature of the discharge line at the
compressor is exceeded?
a. Evaporator superheat will be excessive, causing capacity loss
b. Gassing of the indoor metering device will occur during the cooling cycle
c. Subcooling in the condenser will decline to a dangerously low level
d. Temperature in the compressor will be high enough to vaporize the lubricant -
Correct Solution d (Temperature in the compressor will be high enough to
vaporize the lubricant)
A system should be operated for at least ____ before heat measurements are taken.
a. 20 minutes
, b. 30 minutes
c. 45 minutes
d. 1 hour - Correct Solution a (20 minutes)
What level of vacuum is needed to ensure that a sufficiently deep vacuum has been
drawn for the removal of water vapor?
a. 500 microns
b. 1,000 microns
c. 2,500 microns
d. 25,000 microns - Correct Solution a (500 microns)
What potential problem is associated with the use of dye injected for the purpose
of leak detection?
a. Dye can damage a technician's refrigerant manifold gauges
b. Dye can increase the pumping ratio of the compressor
c. Overuse of dye can change the mixing properties of refrigerant and oil
d. Overuse of due can create acids in the oil
See page 186 - Correct Solution c (Overuse of dye can change the mixing
properties of refrigerant and oil)
What gas must be purged through a refrigerant circuit to prevent the formation of
oxides whenever brazing is being done?
a. Any HFC