Buildings (4.1.1.1) - Shall be
inspected (how often) the
building owner shall
ensure that all areas of
the building containing
water-filled piping shall
be maintained at a
minimum temperature of
40°F and not exposed to
freezing conditions
When the pump is in circulation /heat
operation a small water
leak on the pump
bearings is desirable and
should not be
considered a
malfunction. Additionally,
water should discharge
from a ---- relief valve
(electric pump) or ---
exchanger (diesel pump)
while the fire pump is
operating under a "no-
flow" condition.
https://quizlet.com/1010600572/s12-certificate-of-fitness-sprinkler-2025-updatecomprehensive-questions-and-verified-answers-complete-soluti… 1/133
,2/25/25, 6:10 PM S12 Certificate of Fitness Sprinkler 2025 update|comprehensive questions and verified answers (complete solutions) Exam|G…
fire extinguishing system, other than a water mist
A sprinkler system is a
system, that utilizes water as the extinguishing agent.
Inspection, testing, personally supervised and be performed in
servicing and other accordance with NFPA (National Fire Protection
maintenance of sprinkler Association) #25 2011 edition.
systems must be
All multiple dwellings, fire extinguishers, buckets, axes, fire hooks, fire
factories, office buildings, doors and other means of preventing and
warehouses, stores and extinguishing fires as the commissioner may direct.
offices, theaters and
music halls, hospitals and
asylums, and all public
schools and other public
buildings, churches and
other places where large
numbers of persons are
congregated for
purposes of worship,
instruction, amusement,
and all piers, bulkheads,
wharves, pier sheds,
bulkhead sheds or other
waterfront structures
shall provide
Required fire protection the building or structure is altered. Systems not
systems shall be complying with this section shall be considered to
extended or altered as be impaired.
necessary to maintain
and continued protection
whenever
the physical appearance of fire protection
It shall be unlawful to equipment but that does not perform a fire
install or maintain any fire protection function where it may be confused with
protection system or actual fire protection equipment. An example would
device that has be a CCTV camera that is installed inside a shell that
resembles a sprinkler head
https://quizlet.com/1010600572/s12-certificate-of-fitness-sprinkler-2025-updatecomprehensive-questions-and-verified-answers-complete-soluti… 2/133
,2/25/25, 6:10 PM S12 Certificate of Fitness Sprinkler 2025 update|comprehensive questions and verified answers (complete solutions) Exam|G…
SPRINKLER AND/OR
STANDPIPE SYSTEM
MAINTENANCE AND
INSPECTIONS
1. Automatic and non-
automatic sprinkler
systems shall be
inspected, tested and
maintained as required by
NFPA #25 2011 edition by
a competent person
holding a S-12 Certificate
of Fitness and employed
or contracted by the
owner, to see that all
parts of the system are in
good working order, and
that the Fire Department
connection(s), if any, are
ready for immediate use
by the Fire Department. A
detailed record shall be
kept on the premises or
other approved location,
for a minimum of 3 years
for examination by any
representative of the Fire
Department.
https://quizlet.com/1010600572/s12-certificate-of-fitness-sprinkler-2025-updatecomprehensive-questions-and-verified-answers-complete-soluti… 3/133
, 2/25/25, 6:10 PM S12 Certificate of Fitness Sprinkler 2025 update|comprehensive questions and verified answers (complete solutions) Exam|G…
2.A supply of at least six
extra sprinkler heads shall
be kept available on the
premises, to replace
promptly any fused or
damaged sprinklers. Any
head which has opened
or has been damaged
shall be replaced
immediately with sprinkler
head of similar
characteristics such as
operating temperature,
orifice size, deflector
orientation and thermal
sensitivity.
3. At least once every five
years, the Fire
Department connection
or connections for a
sprinkler system shall be
subjected to a hydrostatic
pressure test to
demonstrate its suitability
for Fire Department use.
The test shall be
arranged to be
conducted by a Master
Fire Suppression Piping
Contractor in the
presence of a Fire
Department
representative.
The contractor shall be
hired by the owner or the
owner's representative.
https://quizlet.com/1010600572/s12-certificate-of-fitness-sprinkler-2025-updatecomprehensive-questions-and-verified-answers-complete-soluti… 4/133