Which agency approves a a.) The Regional Water Quality Board
site-specific variance CCR Title 23, Sec 2681(a)
which allows for an
alternative method of
construction or
monitoring:
a.) The Regional Water
Quality Board
b.) The State Water
Resources Control Board
c.) The Department of
Toxic Substance Control
d.) The local agency
https://quizlet.com/958624076/icc-california-ust-service-technician-exam-newest-2024-actual-exam-300-questions-and-corect-detailed-answers-verifi… 1/60
,10/17/24, 3:33 PM ICC CALIFORNIA UST SERVICE TECHNICIAN EXAM NEWEST 2024 ACTUAL EXAM 300 QUESTIONS AND CORECT DETAIL…
The regulations to enforce b.) California Code of Regulations; Title 23, Chapter 16
compliance of
underground storage tank
systems in the state are
found in?
a.) Code of Federal
Regulations, 40 CFR Part
281
b.) California Code of
Regulations, Title 23,
Chapter 16
c.) Code of Federal
Regulations, 40 CFR Part
280
d.) California Code of
Regulations, Title 23,
Chapter 17
By definition an b.) The tank, all connected piping, ancillary equipment
"underground storage and containment system
tank system" includes
a.) The tank, all connected (H&SC, Sec 25281(z))
piping and dispensers
b.) The tank, all connected
piping, ancillary
equipment and
containment system
c.) Only the tank
d.) Only tanks totally
beneath the surface of the
ground
https://quizlet.com/958624076/icc-california-ust-service-technician-exam-newest-2024-actual-exam-300-questions-and-corect-detailed-answers-verifi… 2/60
,10/17/24, 3:33 PM ICC CALIFORNIA UST SERVICE TECHNICIAN EXAM NEWEST 2024 ACTUAL EXAM 300 QUESTIONS AND CORECT DETAIL…
The written report b.) Cause of the release
submitted to the local CCR Title 23, Sec 2652(c)
agency after an
unauthorized release is
required to include the
following except:
a.) Description of actions
taken to stop the release
b.) Cause of the release
c.) Method of disposal of
released product
d.) Date on which the
release was discovered
An unauthorized release D. All of the above
which does not escape H&SC, Sec 25294
from secondary
containment only requires
a record on the operator's
monitoring reports
provided:
A. It did not increase the
hazard of fire
B. It did not cause any
deterioration of the
secondary containment
C. It was cleaned up within
8 hours of detection
D. All of the above
https://quizlet.com/958624076/icc-california-ust-service-technician-exam-newest-2024-actual-exam-300-questions-and-corect-detailed-answers-verifi… 3/60
, 10/17/24, 3:33 PM ICC CALIFORNIA UST SERVICE TECHNICIAN EXAM NEWEST 2024 ACTUAL EXAM 300 QUESTIONS AND CORECT DETAIL…
The annual monitoring D. A person who meets the requirements of both a
certification may be and b
performed by: CCR Title 23, Sec 2715(i)
A. A person possessing
the appropriate
contractors licenses
B. An individual trained
and certified by the
manufacturer of the
monitoring equipment
C. A designated UST
operator
D. A person who meets
the requirements of both a
and b
When an automatic tank c.) Outside air temperature
gauge is utilized for CCR Title 23, Sec 2643(b)(1)
single-walled tank leak
detection, it shall generate
a post-test hard copy data
report of the following
information, except:
a.) Liquid volume
b.) Fuel depth
c.) Outside air temperature
d.) Time and date of test
If a UST system is utilizing c.) 90%
an overfill alarm, the alarm
must be triggered to alert
the transfer operator when
the tank is no more than
___________ full
a.) 85%
b.) 95%
c.) 90%
d.) 80%
https://quizlet.com/958624076/icc-california-ust-service-technician-exam-newest-2024-actual-exam-300-questions-and-corect-detailed-answers-verifi… 4/60