OPERATOR EXAM ACTUAL 2026/2027
HIGH YIELD PRACTICE QUESTION
1. A low-pressure centrifugal chiller using R-123 shows a condenser approach of 0.5°F,
a leaving chilled-water temperature 2°F above setpoint, and a purge-unit run-time
that has tripled over two weeks. Which conclusion best integrates these three
observations?
A. The chiller is overcharged; excess refrigerant is raising condensing pressure and
forcing the purge to run.
B. Non-condensables are accumulating in the condenser, degrading heat transfer and
causing the purge to cycle frequently.
C. The compressor is surging due to low condenser water flow, and the purge is
responding to pressure instability.
D. The refrigerant charge is low, causing the evaporator to starve and the purge to
remove excess vapor.
Answer: B. Non-condensables are accumulating in the condenser, degrading heat
transfer and causing the purge to cycle frequently.
Rationale: A tight condenser approach (0.5°F) with elevated purge run-time is the classic
signature of non-condensable gas blanketing in a low-pressure machine; the gas raises
condenser pressure and impairs heat transfer, so leaving chilled-water temperature rises
above setpoint. Overcharge (A) would widen approach and raise subcooling, not tighten it.
Surging (C) produces noise and amperage swings, not a tight approach. Low charge (D)
would show high approach and low purge activity, not the opposite.
Page 1 of 26
,2. A reciprocating compressor operating on R-22 has a discharge temperature of
265°F, suction superheat of 40°F, and a condensing temperature of 110°F. Which is the
most likely root cause?
A. Liquid floodback into the suction line is cooling the discharge.
B. Excessive suction superheat is raising discharge temperature beyond safe limits.
C. A restricted liquid line is causing subcooling to drop.
D. The condenser is fouled, raising condensing pressure and discharge temperature.
Answer: B. Excessive suction superheat is raising discharge temperature beyond safe
limits.
Rationale: Discharge temperature is primarily a function of suction superheat and
compression ratio; 40°F superheat is excessive and drives discharge temperature to 265°F,
risking oil breakdown. Liquid floodback (A) would lower, not raise, discharge temperature.
A liquid-line restriction (C) affects subcooling and flash gas, not primarily discharge
temperature. Condenser fouling (D) would raise condensing temperature and discharge
pressure, but the condensing temperature is normal here.
Page 2 of 26
, 3. A two-stage ammonia system with a flash intercooler shows an intermediate
pressure that is 45% of the discharge pressure instead of the ideal geometric mean.
What is the most likely consequence?
A. Increased compressor displacement requirement and reduced system efficiency.
B. Lower discharge temperature and improved volumetric efficiency.
C. Higher evaporator capacity due to increased flash gas.
D. Reduced condenser load and lower total power consumption.
Answer: A. Increased compressor displacement requirement and reduced system
efficiency.
Rationale: The optimal interstage pressure is the geometric mean of suction and discharge
pressures; deviating to 45% of discharge pressure increases the high-stage compression
ratio and reduces volumetric efficiency, raising required displacement and power. Lower
discharge temperature (B) is not guaranteed and does not offset the efficiency loss. Flash
gas (C) increases but reduces net refrigerating effect. Condenser load (D) would not
decrease; total power would rise.
4. During a pump-down test on a low-temperature R-404A rack, the low-pressure
cutout trips at 5 psig but the compressor restarts within 30 seconds repeatedly. Which
control defect best explains this?
A. The anti-short-cycle timer is bypassed or failed.
B. The defrost termination thermostat is stuck closed.
C. The liquid-line solenoid is leaking by.
D. The suction pressure regulator is set too high.
Answer: A. The anti-short-cycle timer is bypassed or failed.
Rationale: Rapid restart after a low-pressure cutout indicates the anti-short-cycle timer is
not enforcing the minimum off-time, allowing immediate restart. A stuck defrost
termination (B) would keep the system in defrost, not cause rapid cycling. A leaking
liquid-line solenoid (C) would prevent pump-down from reaching cutout. A suction
pressure regulator set high (D) would hold suction pressure up, not cause rapid
cutout-restart.