1. Control valves on private fire service mains must be:
A. Listed indicating-type valves
B. Any valve the contractor chooses
C. Non-indicating gate valves without listing
D. Ball valves used for plumbing
Correct Answer: A. Listed indicating-type valves
Rationale: Indicating valves show whether they are open or closed.
2. A post indicator valve (PIV) is:
A. An underground valve with an above-grade post showing 'OPEN' or 'SHUT'
B. A valve inside the sprinkler riser room
C. A pressure relief valve
D. A check valve
Correct Answer: A. An underground valve with an above-grade post showing 'OPEN' or
'SHUT'
Rationale: PIVs allow quick visual confirmation of valve position.
3. Post indicator valves are generally located at least how far from the building they serve?
A. 5 feet
B. 10 feet
C. 40 feet
D. 100 feet
Correct Answer: C. 40 feet
Rationale: This keeps the valve accessible during a fire. A wall PIV may be used where the 40
ft distance is not possible.
TFM10 NFPA 24 | Exam 2 Page 1
, 4. A wall post indicator valve is used when:
A. The valve is a check valve
B. There is insufficient space for a yard PIV and the wall is suitable, with AHJ approval
C. The main is above ground
D. The building has no sprinklers
Correct Answer: B. There is insufficient space for a yard PIV and the wall is suitable, with
AHJ approval
Rationale: The wall location must remain accessible in a fire.
5. An outside screw and yoke (OS&Y) valve indicates that it is open when:
A. The handwheel is removed
B. The stem is fully retracted
C. The valve is painted red
D. The stem is extended out of the yoke
Correct Answer: D. The stem is extended out of the yoke
Rationale: A visible stem shows the gate is raised and the valve is open.
6. Which method is acceptable for supervising control valves in the open position?
A. Electrical supervision (tamper switches), locking or sealing as permitted
B. Removing the handle permanently without supervision
C. Painting the valve
D. Hiding the valve
Correct Answer: A. Electrical supervision (tamper switches), locking or sealing as permitted
Rationale: Supervision reduces the risk of closed valves, a common cause of system failure.
TFM10 NFPA 24 | Exam 2 Page 2
, 7. According to NFPA 25, control valves secured with tamper-evident seals should be
inspected:
A. Daily
B. Annually
C. Every 5 years
D. Weekly
Correct Answer: D. Weekly
Rationale: Locked or electrically supervised valves may be inspected monthly.
8. According to NFPA 25, control valves that are locked or electrically supervised may be
inspected:
A. Never
B. Weekly
C. Every 5 years
D. Monthly
Correct Answer: D. Monthly
Rationale: Valves are also operated annually through their full range and returned to normal.
9. Underground valves with a curb box or roadway box should:
A. Have the box properly aligned and accessible, with a key available
B. Be buried without a box
C. Have no marking
D. Be paved over
Correct Answer: A. Have the box properly aligned and accessible, with a key available
Rationale: Access is needed during emergencies and maintenance.