Testing Calculations Test - Questions with Correct Answers
25 questions
1. Using L = SD√P / 148,000, what is the allowable leakage for 1,000 ft of 8-inch pipe tested at
200 psi?
A. 0.38 gal/h
B. 0.76 gal/h
C. 1.53 gal/h
D. 7.64 gal/h
Correct Answer: B. 0.76 gal/h
Rationale: L = (1,000 x 8 x √200) / 148,000 = (8,000 x 14.14) / 148,000 = 0.76 gal/h.
2. What is the allowable leakage for 2,000 ft of 6-inch pipe tested at 200 psi?
A. 0.57 gal/h
B. 0.86 gal/h
C. 1.15 gal/h
D. 2.29 gal/h
Correct Answer: C. 1.15 gal/h
Rationale: L = (2,000 x 6 x 14.14) / 148,000 = 169,,000 = 1.15 gal/h.
3. What is the allowable leakage for 1,500 ft of 12-inch pipe tested at 225 psi?
A. 1.22 gal/h
B. 1.82 gal/h
C. 2.43 gal/h
D. 18.2 gal/h
Correct Answer: B. 1.82 gal/h
Rationale: L = (1,500 x 12 x √225) / 148,000 = (18,000 x 15) / 148,000 = 1.82 gal/h.
TFM10 NFPA 24 | Hydraulics & Testing Calculations Test Page 1
, 4. The allowable leakage is 0.76 gal/h. What is the total allowable leakage for the full 2-hour
test?
A. 0.38 gal
B. 0.76 gal
C. 1.53 gal
D. 3.04 gal
Correct Answer: C. 1.53 gal
Rationale: 0.76 x 2 = 1.53 gal (using the unrounded 0.764 gal/h).
5. A system's maximum working pressure is 175 psi. What hydrostatic test pressure is
required?
A. 150 psi
B. 175 psi
C. 200 psi
D. 225 psi
Correct Answer: D. 225 psi
Rationale: 175 + 50 = 225 psi, which is greater than 200 psi.
6. A system's maximum working pressure is 120 psi. What hydrostatic test pressure is
required?
A. 120 psi
B. 150 psi
C. 170 psi
D. 200 psi
Correct Answer: D. 200 psi
Rationale: Working pressure does not exceed 150 psi, so the test is at 200 psi.