(Valves, Hydrants, FDCs, Flow Testing & ITM) - Questions
with Correct Answers
25 questions
1. An indicating valve is one that:
A. Shows whether it is open or closed by its position or a target
B. Is always buried
C. Is only used for drains
D. Has no handle
Correct Answer: A. Shows whether it is open or closed by its position or a target
Rationale: PIVs, OS&Y valves and butterfly valves with indicators are examples.
2. Which valve type has a visible stem that rises when opened?
A. Ball valve
B. Outside screw and yoke (OS&Y) gate valve
C. Non-rising stem gate valve without indicator
D. Check valve
Correct Answer: B. Outside screw and yoke (OS&Y) gate valve
Rationale: The visible stem makes position easy to see.
3. Underground non-indicating valves operated by a T-wrench should be:
A. Paved over
B. Unmarked
C. Accessible through a valve box and their location recorded
D. Removed
Correct Answer: C. Accessible through a valve box and their location recorded
Rationale: Valve locations must be known for emergencies.
TFM10 NFPA 24 | Unit Quiz 3 Page 1
, 4. A hydrant 'barrel' is:
A. The paint colour
B. The underground pipe
C. The vertical body of the hydrant above the main valve
D. The cap
Correct Answer: C. The vertical body of the hydrant above the main valve
Rationale: In dry barrel hydrants, the barrel is empty when not in use.
5. The 'bonnet' of a hydrant is:
A. The outlet thread
B. The drain hole
C. The base of the hydrant
D. The top cover of the hydrant, which is colour coded under NFPA 291
Correct Answer: D. The top cover of the hydrant, which is colour coded under NFPA 291
Rationale: Colour coding is applied to the bonnet and caps.
6. According to NFPA 291, Class A hydrants (1,000-1,499 gpm) are painted:
A. Light blue
B. Green
C. Red
D. Orange
Correct Answer: B. Green
Rationale: Colours indicate flow at 20 psi residual.