A+ VERIFIED
Oregon Plumbing Inspector Exam Practice Questions And Correct
Answers (Verified Answers) Plus Rationale Q&A Instant Download Pdf
50 Questions
Clinical | Rationale-Driven - Pass Guaranteed - A+ Graded
50 1 50
QUESTIONS SECTIONS RATIONALES
WHAT THIS COVERS
01 Oregon Plumbing Specialty Code (OPSC) inspection and enforcement
02 BCD/OIC certification rules
03 OAR 918. It emphasizes code administration
04 Plan review
05 Inspection procedures
06 Technical provisions for drainage
ABOUT THIS ASSESSMENT
This exam assesses mastery of the Oregon Plumbing Specialty Code (2021 UPC with Oregon amendments), BCD/OIC certification
rules, ORS 447 and OAR 918. It emphasizes code administration, plan review, inspection procedures, and technical provisions for
drainage, venting, water supply, fixtures, water heaters, backflow, and special wastes.
, EXAMINATION QUESTIONS
SECTION 1 - Oregon Plumbing Specialty Code (OPSC) inspection and enforcement
(Questions 1 to 50)
1. A backflow preventer is installed on a commercial irrigation system. Which test is required at initial inspection under
Oregon cross-connection rules?
A. Dye test
B. Air test
C. Differential pressure test
D. Hydrostatic test
Answer: C [Concept: Oregon Plumbing Specialty Code (OPSC) inspection and enforcement]
Rationale: OAR 333-061 and OPSC require annual testing of backflow assemblies by a certified tester using a differential pressure test
for RPZ and DCVA assemblies. Dye, air, and hydrostatic tests do not verify backflow assembly function. The differential pressure test
confirms the check valve and relief valve performance.
2. Which condition requires a backflow prevention assembly on a boiler feed line per OPSC?
A. Boiler connected to a potable water system with chemical treatment
B. Boiler using only distilled water
C. Boiler with a pressure relief valve
D. Boiler located in a basement
Answer: A [Concept: Oregon Plumbing Specialty Code (OPSC) inspection and enforcement]
Rationale: OPSC requires a reduced-pressure principle backflow prevention assembly (RPBA) or an air gap when a boiler is
connected to a potable water system and chemicals are added, creating a health hazard cross-connection. Distilled water, pressure
relief valves, and basement location alone do not trigger this requirement. The key is the potential for contamination from chemical
treatment.
3. During plan review, a designer proposes a 3-inch horizontal wet vent serving a water closet and lavatory. Which
OPSC provision governs?
A. Wet venting is prohibited for water closets in all cases.
B. The wet vent must be sized per Table 908.1 and the fixture drain must connect downstream.
C. A 3-inch wet vent is always oversized and requires a reduction to 2 inch.
D. Wet venting is allowed only on the top floor of a building.
Answer: B [Concept: Oregon Plumbing Specialty Code (OPSC) inspection and enforcement]
Rationale: UPC Chapter 9 permits horizontal wet venting where the wet vent is sized per Table 908.1 and the fixtures connect in the
prescribed order, with the water closet downstream. A is false because wet venting of water closets is allowed under conditions; C and
D are not code requirements.
4. A 3-inch horizontal storm drain at 1/8 inch per foot slope must convey what maximum roof area in square feet?
A. 1,160 square feet
B. 1,480 square feet
C. 1,700 square feet
D. 2,050 square feet
Answer: B [Concept: Oregon Plumbing Specialty Code (OPSC) inspection and enforcement]
Rationale: UPC Table 1106.2 allows a 3-inch storm drain at 1/8 inch per foot slope to drain 1,480 square feet of roof area. The other
values correspond to different pipe sizes or slopes and are therefore incorrect.
Page 2 | Oregon Plumbing Inspector Exam Practice Questions And Correct Answers (Verified Answers) Plus Rationale Q&A Instant Download Pdf 50